HV100 Series High Performance Current Vector Inverter
51
12.06
Automatic
fault
reset times
The frequency of automatic fault reset is set by 12.06.
When the number of fault resets is set to 0, there is no
automatic reset function, and it can only be reset
manually. When 12.06 is set to 100, the number of times
is unlimited, that is, countless times.
0
~
100
0
×
12.07
Automatic
fault
reset interval
After a fault occurs during operation, the inverter stops
outputting and displays the fault code. After the reset
interval set in 12.07, the inverter automatically resets the
fault and restarts the operation according to the set
starting mode.
0.1
~
60.0s
3.0
×
12.08
Cooling fan control
0: automatic control mode
1: Always running during power-on
2. The fan will work when the temperature is higher than
50
℃
, and the fan will not work when the temperature is
lower than 45
℃
.
0
~
2
0
○
12.09
Password
for
running restricted
function
By default, the password is 0 ,and 12.10 and 12.11 can
be set; When there is a password, 12.10 and 12.11 can
only be set after the password is verified correctly.
0
~
65535
0
○
12.10
Selection
for
running restricted
function
0: Forbid
1:Effective
0
~
1
0
○
12.11
Run limit time
Set Run limit time
0
~
65535(h)
0
×
12.12
Frequency drop
point at
instantaneous
power failure
If the inverter bus voltage drops below 12.12* rated bus
voltage, and the instantaneous stop control is effective,
the instantaneous stop starts to act.
220V:180
~
330V
250V
380V:300
~
550V
450V
Type
setting
×
12.13
Frequency
drop
coefficient
of
instantaneous
power failure
The larger the value is, the faster the frequency reduction
rate is.
0: the instantaneous stop function is invalid.
0
~
100
0
○
12.14
Dropping control
0.00: The droop control function is invalid
When multiple inverters drive the same load, the load
distribution is unbalanced due to different speeds, which
makes the inverters with higher speeds bear heavier
loads. The droop control characteristic is that the speed
droops with the increase of load, which can make the
load evenly distributed; This parameter adjusts the
frequency variation of inverter with drooping speed.
0.00
~
10.00Hz
0.00
×
12.15
Speed
tracking
waiting time
Before the inverter speed tracking starts, start tracking
after the delay.
0.1
~
5.0S
1.0
×
12.16
Speed
tracking
current
limiting
level
In the process of speed tracking, this function code plays
the role of automatic current limiting. When the actual
current reaches the threshold (12.16), the inverter
reduces the frequency and limits the current, and then
continues to track and accelerate; The set value is a
percentage relative to the rated current of the inverter.
80
%
~
200
%
* INV
Rtd current
100%
×