HV100 Series High Performance Current Vector Inverter
35
06.42
AI1 curve
inflection point 2
input
corresponding
setting
-200.0%
~
200.0%
60.0%
○
06.43
AI1 curve
maximum input
【
06.41
】~
10.00
10.00
○
06.44
AI1 curve
maximum input
corresponding
setting
-200.0%
~
200.0%
100.0%
○
06.45
AI2 curve
minimum input
0.00
~
【
06.47
】
0.00
○
06.46
AI2 curve
minimum input
corresponding
setting
-200.0%
~
200.0%
0.0%
○
06.47
AI2 curve
inflection point 1
input
【
06.45
】~
【
06.49
】
3.00
○
06.48
AI2 curve
inflection point 1
input
corresponding
setting
-200.0%
~
200.0%
30.0%
○
06.49
AI2 curve
inflection point 2
input
【
06.47
】~
【
06.51
】
6.00
○
06.50
AI2 curve
inflection point 2
input
corresponding
setting
-200.0%
~
200.0%
60.0%
○
06.51
AI2 curve
maximum input
【
06.49
】~
10.00
10.00
○
06.52
AI2 curve
maximum input
corresponding
setting
-200.0%
~
200.0%
100.0%
○
06.53
AI1 input voltage
protection upper
limit
When the value of analog input AI1 is greater than 06.53,
or AI1 input is less than 06.54, the inverter Y terminal or
relay R outputs "AI1 input overrun" ON signal, which is
used to indicate whether the AI1 input voltage is within
the set range.
0.00V/0.00m
A
~
10.00V/20.0
0mA
6.80
○
06.54
AI1 input voltage
protection lower
limit
0.00V/0.00m
A
~
10.00V/20.0
0mA
3.10
○
007group-digital input and output parameters
Function
code
Name
Content
Setting
range
Factory
Alteration
07.00
Input terminal DI1
function (when
00.01 is 2 or 3, the
default function is
58)
0: None
1: Forward rotation control
(
FWD
)
2: Reverse rotation control
(
REV
)
3: Three-wire control
4: Forward jog control
5: Reverse jog control
6: Free stop control
7: External rest signal input(RST)
0
~
65
1
×