HV100 Series High Performance Current Vector Inverter
29
04.13
Keyboard digital
setting torque
The set value is a percentage of the rated current of
the motor
-200.0%
~
200.0%
0.0%
○
04.14
Speed limit
channel selection
1 for torque control
mode (forward
direction)
0: keypad digital given1
1: AI1
2: AI2
0
~
2
0
○
04.15
Speed limit
channel selection
1 of torque control
mode (reverse
direction)
0: keypad digital given2
1: AI1
2: AI2
0
~
2
0
○
04.16
Keyboard digital
limit speed 1
Keyboard digital limit speed 1 to a limit relative to the
maximum output frequency. This function code
corresponds to the limit value of forward speed when
04.14=0.
0.0
~
100.0%
100.0%
○
04.17
Keyboard digital
limit speed 2
Keyboard digital limit speed 2 to a limit relative to the
maximum output frequency. This function code
corresponds to the limit value of reverse speed when
04.15=0.
0.0
~
100.0%
100.0%
○
04.18
Torque rise time
Torque rise/down time defines the time when the
torque rises from 0 to the maximum value or falls from
the maximum value to 0.
0.0
~
10.0S
0.1
○
04.19
Torque fall time
0.0
~
10.0S
0.1
○
04.20
Electric torque
limitation in vector
mode
Set the Electric torque limit of vector mode, which is a
percentage of the rated current of the motor.
G type: 0.0
%~
200.0
%
160.0%
P type: 0.0
%~
200.0
%
120.0%
Type
setting
○
04.21
Brake torque
limitation in vector
mode
Set the brake torque limit of vector mode, which is a
percentage of the rated current of the motor.
G type: 0.0
%~
200.0
%
160.0%
P type: 0.0
%~
200.0
%
120.0%
Type
setting
○
04.22
Torque detection
action selection
0: Detection invalid
1: Continue to run after detecting torque at constant
speed
2: Continue to run after detecting torque during
operation
3: Cut off the output after the torque is detected at
constant speed
4: Cut off the output after detecting torque in operation
5: Continue running after insufficient torque is
detected at constant speed
6: Continue to run after insufficient torque is detected
during operation
7: Cut off the output after detecting insufficient torque
at constant speed
8: Cut off the output after detecting insufficient torque
during operation
0
~
8
0
×
04.23
Torque detection
level
When the actual torque is within 04.24 (torque
detection time) and continuously exceeds 04.23
(torque check out level), the inverter will make
corresponding actions according to the setting of
04.22. When the set value of torque detection level is
100%, it corresponds to the rated torque of the motor.
G type: 0.0
%~
200.0
%
150.0%
P type: 0.0
%~
200.0
%
110.0%
Type
setting
×
04.24
Torque detection
time
0.0
~
10.0S
0.0
×
04.25
Cutoff frequency
of static friction
coefficient
As the starting torque of the motor is not enough,
increasing the set value of 04.26 can increase the
starting torque. When the speed exceeds the set
value of 04.25, the increased torque will slowly
decrease to the given torque within the set time of
04.27.
0.00
~
300.00Hz
10.00
○
04.26
Setting of static
friction coefficient
0.0
~
200.0
0.0
○