HV100 Series High Performance Current Vector Inverter
30
04.27
Static friction
coefficient
maintenance time
0.00
~
600.00s
0.00
×
005Group-V/F Control Parameter
Function
code
Name
Content
Setting range
Factory
Alteration
05.00
V/F curve setting
0: Linear curve
1: Torque reduction curve 1(1.3 power)
2: Torque reduction curve 1(1.5 power)
3: Torque reduction curve 1(1.7 power)
4: Square curve
5: V/F curve set by user (determined from 05.01 to
05.06)
0
~
5
0
×
05.01
Torque boost
setting
Manual torque boost. This setting is a percentage
relative to the rated voltage of the motor.
0.0
~
30.0
%
Model
setting
×
05.02
Torque boost
cutoff frequency
Set Cutoff frequency of torque boost
0.00
~
Rated
frequency
15.00
×
05.03
V/F frequency F1
0.00
~
Frequency
value F2
12.50
×
05.04
V/F voltage V1
0.0
~
V2
25.0%
×
05.05
V/F frequency F2
Frequency
value 01
~
Frequency
value F3
25.00
×
05.06
V/F voltage V2
V1
~
V3
50.0%
×
05.07
V/F frequency F3
Frequency
value 01
~
【
02.02
】
37.50
×
05.08
V/F voltage V3
V2
~
100.0
%
*
rated volt
75.0%
×
05.09
V/F control slip
frequency
compensation
The speed of asynchronous motor will decrease after
being loaded. Slip compensation can make the speed
of motor close to its synchronous speed, thus making
the speed control accuracy of motor higher.
0.0
~
200.0
%
*
rated speed
0.0%
○
05.10
V/F control slip
frequency filter
coefficient
This parameter is used to adjust the response speed
of slip frequency compensation. The larger the setting
of this value, the slower the response speed and the
more stable the motor speed.
1
~
10
3
○
05.11
V/F control torque
frequency
compensation
filter coefficient
When the free torque increases, this parameter is
used to adjust the response speed of torque
compensation. The larger this value is, the slower the
response speed and the more stable the motor speed.
0
~
10
Type
setting
○