HV100 Series High Performance Current Vector Inverter
59
Operation control is implemented by multi-function terminals defined as FWD, REV, JOG forward rotation, JOG
reverse rotation and other functions.
2
:
Communication operation command channel
Operation control is implemented by the upper controller through communication.
Notes:
Even in the running process, by modifying the set value of the function code, the running command channel can be
changed. Please set it carefully!
00.04
Selection of main frequency source A
0
~
11
9
0: Digital setting 1 (press keyboard key
, 00.10)
The
initial value of frequency setting is 00.09, which can be adjusted by using operation panel key or digital
encoder. The modified frequency value will be stored in 00.09 after power failure (if you want this frequency not to be stored,
you can set 00.07 to 1.
1: Digital setting 2(UP/DOWN te00.10)
The initial value of frequency setting is 00.10, and the operating frequency is changed by the on-off of multifunctional
terminals externally defined as UP/DOWN function (see 07 Group X terminal frequency increasing and decreasing item
function number for details). When the UP terminal and COM terminal are closed, the frequency rises; When the DOWN
terminal and COM terminal are closed, the frequency drops; The frequency remains unchanged when the UP/DOWN
terminal is closed or disconnected from the COM terminal at the same time. If frequency power-down storage is set, the
modified frequency value will be stored in 00.10 after power-down. The rate at which the UP/DOWN terminal modifies the
operating frequency can be set by function code 07.12.
Tips
:
Whether
it is panel key adjustment or terminal UP/DOWN adjustment, the set value is superimposed with an
adjustment amount on the basis of 00.09 or 00.10, and the final frequency output value is from the lower limit frequency to
the maximum output frequency. The adjustment amount of terminal UP/DOWN adjustment can be cleared by selecting 0
for the UP/DOWN terminal frequency through X terminal. The
M-FUNC
adjustment
amount of the panel can
also be cleared by selecting the clear key frequency setting.
2: Digital setting 3 (communication setting)
Change the set frequency through the serial port frequency setting command. See Group 011 communication
parameters for details.
3: AI1 analog setting (0 ~ 10V/20mA)
The frequency setting is determined by the analog voltage/current of AI1 terminal, and the input range is:
See the definition of function 06.00 ~ 06.05 for the related setting of DC 0 ~ 10V/20mA.
4: AI2 analog setting (0 ~ 10V)
The frequency setting is determined by the analog voltage/current of AI1 terminal, and the input range is:
See definition of function code 06.06 ~ 06.11 for related setting of DC 0 ~ 10 V.
5: Pulse setting(0~50Hz)
The frequency setting is determined by the terminal pulse frequency (it can only be input by DI6, see 07.05 definition),
and the input pulse signal specification: the high level range is 15 ~ 30V; The frequency range is 0 ~ 50khz. See the
definition of function code 06.15 ~ 06.20 for related settings.
6
:
Simple PLC
To select the given frequency mode of simple PLC, it is necessary to set the function code 09.00 ~ 09.05; Function
codes 09.06 ~ 09.21 are used to determine the operating frequency of each stage of PLC, and function codes 09.22 ~
09.53 respectively define the acceleration and deceleration time and operation time of each stage of PLC.
7
:
Multi- speed settings
Choose this frequency setting mode, and the inverter runs in multi-speed mode. It is necessary to set F7 group “X
terminal as multi-speed selection”and 009 groups of “multi-speed frequency” function codes to determine the
corresponding relationship between a given number of multi-speed segments and a given frequency.
8: PID control
If this frequency setting mode is selected, the operation mode of inverter is process PID control. At this time, 008 sets
of process PID parameters and analog given and pulse given related function codes need to be set. Operating frequency of
inverter is the frequency value after PID action. Please refer to the detailed description of 008 group functions for specific
settings.
9: Keyboard potentiometer setting
The operating frequency is adjusted by operating the potentiometer on the keyboard, and the adjusting frequency
range of the potentiometer is fixed from 0 to the maximum output frequency [00.12].
10: MPPT given
(
Solar water pump
)
11: Potentiometer