HV100 Series High Performance Current Vector Inverter
33
06.12
Analog input
anti-shake
deviation limit
When the analog input signal fluctuates frequently near a
given value, the frequency fluctuation caused by this
fluctuation can be suppressed by setting 06.12.
0.00V
~
10.00V
0.00
○
06.13
Zero frequency
operation
threshold
When 00.15=1 (high frequency mode), the maximum
value of this function code is 500.0Hz.
Zero
frequency
backlash
~
50.00Hz
0.00
○
06.14
Zero frequency
return difference
Set Zero frequency return difference
0.00
~
Zero
frequency
operation
threshold
0.00
○
06.15
External pulse
input corresponds
to physical
quantity
0: Speed command
(
output frequency
,
-100.0%
~
100.0%
)
1: Torque command
(
output torque
,
-200.0%
~
200.0%
)
0
~
1
0
×
06.16
Lower limit of
external pulse
input
Set the input lower limit frequency of external pulse HDI
0.00
~
50.00kHz
0.00
○
06.17
The lower limit of
external pulse
corresponds to the
setting of physical
quantity
Set the external pulse HDI lower limit to the
corresponding setting, which is a percentage relative to
the maximum output frequency.
-200.0%
~
200.0%
0.0%
○
06.18
upper limit of
external pulse
input
Set the upper limit frequency of external pulse HDI input
0.00
~
50.00kHz
50.00
○
06.19
The upper limit of
external pulse
corresponds to the
setting of physical
quantity
Set the external pulse HDI upper limit to the
corresponding setting, which is a percentage relative to
the maximum output frequency.
-200.0%
~
200.0%
100.0%
○
06.20
External pulse
input filtering time
Set External pulse input filtering time
0.00S
~
10.00S
0.05
○
06.21
Function Selection
of AO1
Multifunctional
Analog Output
Terminal
0: Output frequency (before slip compensation)
1: Output frequency (after slip compensation)
2: Set frequency
3: Motor speed (estimated value)
4: Output current
5: Output voltage
6: DC Bus Voltage
7: PID given value
8: PID feedback value
9: AI1
10: AI2
11: Input pulse frequency
12: Torque current
13: Flux current
14: Communication setting
0
~
14
0
○
06.22
Function Selection
of AO2
Multifunctional
Analog Output
Terminal
0
~
14
4
○
06.23
Function selection
of HDO
multi-function
pulse output
terminal
0
~
14
11
○
06.24
AO1 output lower
limit corresponds
to physical
quantity
Set AO1 output lower limit corresponds to physical
quantity
-200.0%
~
200.0%
0.0%
○
06.25
AO1 output lower
limit
Set AO1 output lower limit
0.00
~
10.00V
0.00
○
06.26
AO1 output upper
limit corresponds
to physical
quantity
Set AO1 output upper limit corresponds to physical
quantity
-200.0%
~
200.0%
100.0%
○