HV100 Series High Performance Current Vector Inverter
53
12.25
Special function
LED single digit: AO2 and DO selection
0: AO2 Effective
1: DO Effective
LED10 digit: IPM Fault setting
0: Shield the fault
1: the fault is Effective
LED100 digit: input phase failure rest selection
0: Unable to reset
1: it can be reset after the power supply is normal
LED1000 digit: Reserved
000
~
110
010
×
12.26
Upper
limit
frequency
of
oscillation
suppression
Set Upper limit frequency of oscillation suppression
0.00
~
300.00Hz
50.00
○
12.27
Oscillation
suppression
coefficient
When 12.19 kilobits =1 (oscillation suppression mode
1), the PWM mode is forced to be five-segment; When
12.19 kilobits =2 (oscillation suppression mode 2), the
original mode remains unchanged, and these two modes
can be adjusted by oscillation suppression coefficient
(12.27). In special occasions, if the first two modes cant
suppress the oscillation, use the oscillation suppression
mode 3 (12.19 thousands of bits =3 ), and adjust it
together with the parameters 12.27 (oscillation
suppression coefficient) and 12.28 (oscillation
suppression voltage).
1
~
500
50
○
12.28
Oscillation
suppression
voltage
0.0
~
25.0%*
Rtd volt
5.0
○
12.29
Wave-by-wave
current limiting
and
anti-overvoltage
action options
LED single digit: Selection of wave by wave current
limiting acceleration
0: Forbid
1:Effective
LED10 digit: Selection in wave by wave current limiting
deceleration
0: Forbid
1:Effective
LED100 digit: Selection of wave by wave current limiting
and constant speed
0: Forbid
1:Effective
LED1000 digit: Anti-overvoltage action selection
0: Forbid
1:Effective
0000
~
1111
011
○
12.30
Special
function
selection
LED single digit: Direct-Start function select
0: Forbid
1: Effective
LED 10 digit: display selection of over-torque alarm A-05
0: Forbid
1: Effective
LED100 digit: Reserved
LED1000 digit: Reserved
00
~
11
Type
setting
○
013 Group-Reserved
014 Group Keypad function setting and parameter management
Function
code
Name
Content
Setting
range
Factory
Alteration
14.00
M-FUNC function
selection
0: JOG(Point control)
1: Forward/Reverse switch
2: Clear”▲/▼ “frequency setting
3: Local/Remote operation switch(Reserved)
4: Reverse direction
0
~
4
0
×
14.01
STOP/RST
key
function Selection
0: Only valid for keypad control
1: Effective for both keypad and terminal control
2: Effective for keypad and communication control
3: Valid for all control modes
0
~
3
3
○