![VeEX MPA User Manual Download Page 633](http://html2.mh-extra.com/html/veex/mpa/mpa_user-manual_3826057633.webp)
Protocol Tabs
633
2. When testing lo
w speed Ethernet bandwidths (≤ 1Gbps), you may need to
configure the
Resolution
setting in conjunction with the
Consecutive Bad Time
Required
setting, to ensure that at least one Ethernet packet is received within
the configured period of time (measurement window). The following options are
available:
High (.1 ms), Medium (1 ms)
and
Low (10 ms)
.
When receiving fewer packets per second (lower bandwidths), a lower
resolution setting (larger window of time) is required.
Invert the number of packets per second being received to determine the
time between each received packet, and select the Resolution setting that best
allows for at least packet to be received within the selected measurement
window.
Important: The Resolution setting is only displayed on ports that support
Ethernet rates ≤ 1Gbps.
3. Select
Consecutive Good Time Required
and enter a time interval ranging
from 10 milliseconds to 1638.3 milliseconds. This function allows you to enter the
time-duration (in milliseconds) of consecutive error-free frames to elapse before
Protection Switch measurements stop accumulating.
4. Select
Consecutive Bad Time Required
and enter a time interval ranging from
0.1 milliseconds to 1638.3 milliseconds. This function allows you to enter the
time-duration (in milliseconds) of consecutive errored frames (or no frames) to
elapse before Protection Switch measurements begin to accumulate.
5. From the
Action
box, select
State
. The Select APS Action dialog box appears.
or
to begin measuring. The test set will
begin monitoring the incoming signal for the event. If it occurs, the protection
switch state and time will appear in both seconds and frames present. The
results will not include the number of good frames, but the number of errored
frames that occur before the first good frame. This is based on the previously
selected criteria for consecutive good and bad time parameters.
7. In the
Protection Switch Time (MilliSecs)
table, view the duration, in
milliseconds, that it took for the service disruption to occur.
8. In the
History Recent MilliSeconds table
, view a history of the 10 most recent
measurements.
9. The complete summary of service disruption events for all processors within the
test unit can be viewed simultaneously by selecting the
System
tab and
choosing
Service Disruption
.
MPA_e_manual_D07-00-129P_RevA00
Summary of Contents for MPA
Page 2: ...MPA_e_manual_D07 00 129P_RevA00...
Page 10: ...MPA_e_manual_D07 00 129P_RevA00...
Page 82: ...MPA_e_manual_D07 00 129P_RevA00...
Page 110: ...MPA_e_manual_D07 00 129P_RevA00...
Page 134: ...MLD Tab 134 100G RS FEC Ethernet 400G RS FEC Ethernet MPA_e_manual_D07 00 129P_RevA00...
Page 255: ...Protocol Tabs 255 MPA_e_manual_D07 00 129P_RevA00...
Page 256: ...OTN Tab 256 MPA_e_manual_D07 00 129P_RevA00...
Page 748: ...MPA_e_manual_D07 00 129P_RevA00...
Page 796: ...MPA_e_manual_D07 00 129P_RevA00...