90
Connection Examples
Section 4-5
Communication Settings
• V530-R150
page 194
• Programmable Controller:
Turn OFF the DIP switch of CQM1H.
Set DM6645 to [1001], DM6646 to [0904], DM6648 to [1000] and
DM6649 to [0D00].
Match communication settings with the V530-R150. Refer to the
operation manual for CQM1H for the ways to change the setting.
Program Examples
This is an example of a program in which a Programmable Controller
(CQM1H) receives the data which is read at a V530-R150.
1,2,3...
1.
Set the reading conditions of the V530-R150 and set the reading
mode to RUN mode.
2.
The synchronous sensor or trigger input of the console sends the
reading trigger to the V530-R150.
The V530-R150 reads the code and outputs data.
3.
The data received from the CQM1H is saved in order from the
highest digit in DM0200 from the first bit.
Item
Setting
Baud rate
19200 bps
Data length
8 bit
Parity bits
EVEN
Stop bits
2 bit
Header
None
Footer
CR
Mode
Normal
Clears DM0200 to
DM0220.
Stores reading data in
order from DM0200.