App-18
Appendix-1 Parameter List
Appe
ndix
Others
b060
Window comparator
FV upper limit level
Set an upper limit level.
Setting range: 0 to 100
Lower limit: Lower limit level + Hysteresis
width × 2
100.
Yes
Yes
%
b061
Window comparator
FV lower limit level
Set a lower limit level.
Setting range: 0 to 100
Upper limit: Upper limit level - Hysteresis
width × 2
0.
Yes
Yes
%
b062
Window comparator
FV hysteresis width
Set a hysteresis width for the upper and
lower limit levels.
Setting range: 0 to 10
Upper limit: (Upper limit level - Lower limit
level) × 2
0.
Yes
Yes
%
b063
Window comparator
FI upper limit level
Set an upper limit level.
Setting range: 0 to 100
Lower limit: Lower limit level + Hysteresis
width × 2
100.
Yes
Yes
%
b064
Window comparator
FI lower limit level
Set a lower limit level.
Setting range: 0 to 100
Upper limit: Upper limit level - Hysteresis
width × 2
0.
Yes
Yes
%
b065
Window comparator
FI hysteresis width
Set a hysteresis width for the upper and
lower limit levels.
Setting range: 0 to 10
Upper limit: (Upper limit level - Lower limit
level) × 2
0.
Yes
Yes
%
b066
Window comparator
FE upper limit level
Set an upper limit level.
Setting range: -100 to 100
Lower limit: Lower limit level + Hysteresis
width × 2
100.
Yes
Yes
%
b067
Window comparator
FE lower limit level
Set a lower limit level.
Setting range: -100 to 100
Upper limit: Upper limit level - Hysteresis
width × 2
-100.
Yes
Yes
%
b068
Window comparator
FE hysteresis width
Set a hysteresis width for the upper and
lower limit levels.
Setting range: 0 to 10
Upper limit: (Upper limit level - Lower limit
level) × 2
0.
Yes
Yes
%
b070
Analog operation
level at FV
disconnection
0. to 100./no (ignored)
no
No
Yes
⎯
b071
Analog operation
level at FI
disconnection
0. to 100./no (ignored)
no
No
Yes
⎯
b072
Analog operation
level at FE
disconnection
-100. to 100./no (ignored)
no
No
Yes
⎯
Parameter
No.
Function name
Monitor or data range
Default
setting
Changes during
operation
Unit
Page
Normal b031 = 10
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......