3-22
3-7 Parameter List
3
Operation
Extended Function Mode
Parameter
No.
Function name
Monitor or data range
Default
setting
Changes during
operation
Unit
Page
Normal b031 = 10
Basic setting
A001
Frequency reference
selection
00: Digital Operator (FREQ adjuster)
(Enabled when 3G3AX-OP01 is used.)
01: Terminal
02: Digital Operator (F001)
03: ModBus communication
04: Option 1
05: Option 2
06: Pulse train frequency
07: Not used
10: Operation function result
02
No
No
⎯
A002
RUN command
selection
01: Terminal
02: Digital Operator (F001)
03: ModBus communication
04: Option 1
05: Option 2
02
No
No
⎯
A003
Base frequency
30. to Maximum frequency [A004]
60.
No
No
Hz
A203
* 2nd base frequency 30. to 2nd maximum frequency [A204]
60.
A303
* 3rd base frequency 30. to 3rd maximum frequency [A304]
60.
A004
Maximum frequency
30. to 400.
60.
No
No
Hz
A204
* 2nd maximum
frequency
30. to 400.
60.
A304
* 3rd maximum
frequency
30. to 400.
60.
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......