3-7 Parameter List
3
Operation
Multi-function
o
u
tp
ut termina
l
C021
Multi-function output
terminal
P1 selection
00: RUN (signal during RUN)
01: FA1 (constant speed arrival signal)
02: FA2 (over set frequency arrival signal)
03: OL (overload warning)
04: OD (excessive PID deviation)
05: AL (alarm output)
06: FA3 (set-frequency-only arrival signal)
07: OTQ (overtorque)
08: IP (signal during momentary power interruption)
09: UV (signal during undervoltage)
10: TRQ (torque limit)
11: RNT (RUN time over)
12: ONT (Power ON time over)
13: THM (thermal warning)
19: BRK (brake release)
20: BER (brake error)
21: ZS (0 Hz signal)
22: DSE (excessive speed deviation)
23: POK (position ready)
24: FA4 (set frequency exceeded 2)
25: FA5 (set frequency only 2)
26: OL2 (overload warning 2)
27: FVDc (analog FV disconnection detection)
28: FIDc (analog FI disconnection detection)
29: FEDc (analog FE disconnection detection)
31: FBV (PID FB status output)
32: NDc (network error)
33: LOG1 (logic operation output 1)
34: LOG2 (logic operation output 2)
35: LOG3 (logic operation output 3)
36: LOG4 (logic operation output 4)
37: LOG5 (logic operation output 5)
38: LOG6 (logic operation output 6)
39: WAC (capacitor life warning signal)
40: WAF (cooling fan life warning signal)
41: FR (starting contact signal)
42: OHF (fin overheat warning)
43: LOC (light load detection signal)
44: Not used
45: Not used
46: Not used
47: Not used
48: Not used
49: Not used
50: IRDY (operation ready signal)
51: FWR (forward run signal)
52: RVR (reverse run signal)
53: MJA (fatal fault signal)
54: WCFV (window comparator FV)
55: WCFI (window comparator FI)
56: WCFE (window comparator FE)
(When C062 is used to select the alarm code
output, the multi-function output terminals P1 to
P3, or P1 to P4 are forcibly changed to AC0 to
AC2 or AC0 to AC3 [Acn 'Alarm code output'],
respectively.)
00
No
Yes
⎯
C022
Multi-function output
terminal P2 selection
01
C023
Multi-function output
terminal P3 selection
03
C024
Multi-function output
terminal P4 selection
07
C025
Multi-function output
terminal P5 selection
40
C026
Relay output (MA,
MB) function
selection
05
Parameter
No.
Function name
Monitor or data range
Default
setting
Changes during
operation
Unit
Page
Normal b031 = 10
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......