3-23
3-7 Parameter List
3
Operation
Analo
g
inpu
t, Others
A005
FV/FI selection
00: Switches between FV/FI via terminal AT
01: Switches between FV/FE via terminal AT
02: Switches between FV/FREQ adjuster via
terminal AT
(Enabled only when 3G3AX-OP01 is
used)
03: Switches between FI/FREQ adjuster via
terminal AT
(Enabled only when 3G3AX-OP01 is
used)
04: Switches between FE/FREQ adjuster via
terminal AT
(Enabled only when 3G3AX-OP01 is
used)
00
No
No
⎯
A006
FE selection
00: FE only
01: FV/FI auxiliary frequency reference
(not reversible)
02: FV/FI auxiliary frequency reference
(reversible)
03: FE disabled
03
No
No
⎯
A011
FV start frequency
0.00 to 99.99
100.0 to 400.0
0.00
No
Yes
Hz
A012
FV end frequency
0.00 to 99.99
100.0 to 400.0
0.00
No
Yes
Hz
A013
FV start ratio
0. to FV end ratio
0.
No
Yes
%
A014
FV end ratio
FV start ratio to 100.
100.
No
Yes
%
A015
FV start selection
00: External start frequency
(A011 set value)
01: 0 Hz
01
No
Yes
⎯
A016
FV, FE, FI sampling
1. to 30.
31. (with 500 ms filter ± 0.1 Hz hysteresis)
31.
No
Yes
⎯
A017
Not used
Use "00".
* Do not change.
00
No
No
⎯
⎯
Parameter
No.
Function name
Monitor or data range
Default
setting
Changes during
operation
Unit
Page
Normal b031 = 10
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......