4-84
4-2 Function Mode
4
Functions
Examples of connections and timing of commercial switching operation
Timing example of switching from
Timing example of switching from
Inverter to commercial power
commercial power to Inverter
NFB
ELBC
MC2
MC1
R
S
T
Ro
To
FS
FV
FC
FW
RV
CS
SC
FWY
RVY
CSY
MA
MB
MC
U
V
W
MC3
THRY
Motor
MC1
MC2
MC3
FW
CS
MC1
MC2
MC3
FW
CS
ON
ON
ON
ON
ON
Operation
Inverter output
frequency
Interlock time of MC2 and MC3
(0.5 to 1 s)
ON
ON
ON
OFF
0.5 to 1 s
Retry wait time b003
Operation
Operates after frequency matching.