4-139
4-4 Communication Function
4
Func
tions
4-4 Communication Function
• This function allows the Inverter to communicate with an external controller via the RS485 interface
from the TM2 terminal on the Inverter's control terminal block board.
Communication Specifications
Item
ASCII method
ModBus-RTU method
Note
Transmission speed
2400/4800/9600/19200 bps
Select using
the Digital Operator.
Communication
method
Half-duplex communication
Synchronous system
Start-stop synchronous system
Asynchronous system
Transmission code
ASCII code
Binary
Transmission mode
LSB first
Compatible interface
RS-485
Data bit length
7 or 8 bits
8 bits
Select using
the Digital Operator.
Parity
No parity/Even/Odd
Select using
the Digital Operator.
Stop bit length
1 or 2 bits
Select using
the Digital Operator.
Starting method
One-side start using host command
Wait time
10 to 1000 [ms]
0 to 1000 [ms]
Set using
the Digital Operator.
Connection
1:N (N = 32 max.)
Use the Digital Operator
to select a station No.
Error check
Overrun/Framing
BCC/Vertical/Horizontal parity
Overrun/Framing
CRC-16/Horizontal parity
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......