2-11
2-2 Wiring
2
De
sign
* If multi-function input terminal S3 has not been connected or disconnected, or if the signal logic is
not matched, the Inverter activates an emergency shutoff trip [E37. *]. After checking the cable
connection and the signal logic, input the reset signal (RS).
Emergency shutoff trip [ E37. * ] can be reset only by the reset signal (RS) via multi-function input
terminal S1. (It cannot be reset with the Digital Operator.)
• To enable this function, set the slide switch SW1 lever in the Inverter to [ON].
(With the factory default setting, slide switch SW1 is [OFF]. [This function is disabled.])
* Before operating slide switch SW1, make sure that the input power supply is OFF.
*1. With the terminal with input terminal selection [18 (RS)], NO/NC selection is fixed to [00 (NO)].
*2. When [C003] is [64 (EMR)], [C013] is fixed to [01 (NC)].
*3. If [18 (RS)] has been allocated to a multi-function input terminal (except for S3) other than S1
before switch SW1 is set to "ON", the input terminal selection for the relevant terminal will be
automatically changed to "no (no allocation)" by setting SW1 to "ON". This is done in order to
prevent duplicated allocation of this function. Then, even if SW1 is reset to [OFF], the initial
allocation cannot be restored. Re-allocate the terminal function.
Example) When the multi-function input terminal S2 [C002] is [18 (RS)], setting SW1 to [ON]
changes the [C002] setting to [no (no allocation)]. [18 (RS)] will be allocated to the multi-
function input terminal S1 [C001].
Then, even if SW1 is reset to [OFF], the multi-function input terminal S2 [C002] setting is [no
(no allocation)], and the multi-function input terminal S1 [C001] setting is [18 (RS)].
*4. Input terminal selection [64 (EMR)] cannot be selected with the Digital Operator. When slide
switch SW1 is set to [ON], this function will be automatically allocated.
Slide switch SW1 setting and status of multi-function input terminals S1 and S3
Slide switch
(SW1)
setting
Multi-function input terminal S1
Multi-function input terminal S3
Multi-function input 1
selection
[ C001 ]
Multi-function input 1
operation selection
[ C011 ]
*1
Multi-function input 3
selection
[ C003 ]
Multi-function input 3
operation selection
[ C013 ]
*1 *2
SW1 OFF
Emergency
shutoff:
Disabled
(factory
default)
[Can be selected
randomly]
*4
[Can be selected
randomly]
*4
[Can be selected
randomly]
*4
[Can be selected
randomly]
*4
Factory
default
01 (RV)
Factory
default
00 (NO)
Factory
default
12 (EXT)
Factory
default
00 (NO)
SW1 ON
Emergency
shutoff:
Enabled
*5
Automatic allocation to multi-function input terminals S1 and S3,
and the input terminal with 18 (RS) setting
*3
Fixed
function
(Cannot
be
changed)
18 (RS)
Fixed
function
(Cannot
be
changed)
00 (NO)
Fixed
function
(Cannot
be
changed)
64 (EMR)
Fixed
function
(Cannot
be
changed)
01 (NC)
Turning SW1
on, and then
off
Emergency
shutoff:
Disabled
*3 *5
[Can be selected
randomly]
*4
[Can be selected
randomly]
*4
[Can be selected
randomly]
*4
[Can be selected
randomly]
*4
Holds
setting
while SW1
is ON.
18 (RS)
Holds
setting
while SW1
is ON.
00 (NO)
Emergency
shutoff
function:
Reset
no
(no
allocation)
Holds
setting
while SW1
is ON.
01 (NC)
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......