4-170
4-4 Communication Function
4
Functions
0014h
FA1 (constant speed arrival signal)
R
1: ON
0: OFF
0015h
FA2 (over set frequency arrival
signal)
R
1: ON
0: OFF
0016h
OL (overload warning)
R
1: ON
0: OFF
0017h
OD (excessive PID deviation)
R
1: ON
0: OFF
0018h
AL (alarm signal)
R
1: ON
0: OFF
0019h
FA3 (set-frequency-only arrival
signal)
R
1: ON
0: OFF
001Ah
OTQ (overtorque)
R
1: ON
0: OFF
001Bh
IP (during momentary power
interruption)
R
1: ON
0: OFF
001Ch
UV (during undervoltage)
R
1: ON
0: OFF
001Dh
TRQ (during torque limit)
R
1: ON
0: OFF
001Eh
RNT (RUN time exceeded)
R
1: ON
0: OFF
001Fh
ONT (ON time exceeded)
R
1: ON
0: OFF
0020h
THM (thermal warning)
R
1: ON
0: OFF
0021h
Not used
⎯
0022h
Not used
⎯
0023h
Not used
⎯
0024h
Not used
⎯
0025h
Not used
⎯
0026h
BRK (brake release)
R
1: ON
0: OFF
0027h
BER (brake error)
R
1: ON
0: OFF
0028h
ZS (0 Hz signal)
R
1: ON
0: OFF
0029h
DSE (excessive speed deviation)
R
1: ON
0: OFF
Coil No.
Item
R/W
Description
*1. When either the control circuit terminal block or the coil is turned on, these settings are ON.
The control circuit terminal block has the priority for the multi-function input terminals.
If the master cannot reset the coil ON status because of communication disconnection, turn the control
circuit terminal block from ON to OFF to turn off the coil.
*2. The communications error is retained until a fault reset is input. (Can be reset during operation.)
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......