3-50
3-7 Parameter List
3
Operation
Control parameter
H001
Auto-tuning selection
00: Disabled
01: Not rotate
02: Rotate
00
No
No
⎯
H002
Motor parameter
selection
00: Standard motor parameter
01: Auto-tuning parameter
02: Auto-tuning parameter
(online auto-tuning enabled)
00
No
No
⎯
H202
* 2nd motor
parameter selection
00
H003
Motor capacity
selection
0.20 to 160.0
Factory
default
No
No
kW
H203
* 2nd motor capacity
selection
Factory
default
H004
Motor pole number
selection
2/4/6/8/10
4
No
No
Pole
H204
* 2nd motor pole
number selection
4
H005
Speed response
0.001 to 9.999/10.00 to 80.00
(10.000 to 80.000)
1.590
Yes
Yes
⎯
H205
* 2nd speed
response
1.590
Parameter
No.
Function name
Monitor or data range
Default
setting
Changes during
operation
Unit
Page
Normal b031 = 10
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...