4-52
4-2 Function Mode
4
Functions
RUN Time/Power ON Time Exceeded
• If the total RUN time of the Inverter exceeds the time set in ON time setting b034, a RUN/Power
ON 'time exceeded' (RNT/ONT) signal is output.
RUN Time Exceeded (RNT)
• Allocate 11 (RNT) to any of multi-function output terminals P1 to P5 (C021 to C025) or the relay
output terminal (C026).
• Set a time in RUN time/Power ON time setting b034.
Power ON Time Exceeded (ONT)
• Allocate 12 (ONT) to any of multi-function output terminals P1 to P5 (C021 to C025) or the relay
output terminal (C026).
• Set a time in RUN time/Power ON time setting b034.
Rotation Direction Limit Selection
• Limits motor rotation directions.
• Enabled in either "control circuit terminal block" or "Digital Operator" control mode.
• When a limited RUN command is input, the Digital Operator displays
.
Parameter No.
Function name
Data
Default setting
Unit
b034
RUN time/Power ON
time setting
0.: Does not operate.
0
⎯
1. to 9999.:
Set in increments of 10 hours.
1000 to 6553:
Set in increments of 100 hours.
(100000 to 655300 hours)
Related functions
C021 to C025, C026, d016, d017
OkOkOkO
Parameter No.
Function name
Data
Default setting
Unit
b035
Rotation direction limit
selection
00: Forward and Reverse are enabled.
01: Only Forward is enabled.
02: Only Reverse is enabled.
00
⎯
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......