3-7
3-3 Test Run Operation
3
Operation
Parameter Initialization
• Initialize the parameters using the following procedure.
• To initialize the parameters, set parameter b084 to "02".
Key sequence
Display example
Description
Power On
Press the Mode key once, and then press the Decrement key three
times to display "b---".
Press the Mode key.
"b001" is displayed.
Use the Increment or Decrement key to display "b084".
Press the Mode key. The set value in "b084" is displayed.
Use the Increment or Decrement key to display "02".
Press the Enter key. The set value is entered and "b084" is displayed.
Press the STOP/RESET key while holding down the Mode and
Decrement keys simultaneously.
When the display blinks, release the STOP/RESET key first, and then
the Mode and Decrement keys.
Displays initialization.
(In 1 s)
The parameter number is displayed again in approximately 1 s.
k0.0
bk-k-k-
bk0k0k1
bk0k8k4
0k0
0k2
bk0k8k4
=k.k0k0
dk0k0k1