4-28
4-2 Function Mode
4
Functions
• If the RUN command is turned on with the frequency reference established (or a value larger than
the A052 setting is input), the initial operation is set to normal output.
• The operation to return to normal varies depending on the setting of DC injection braking power
A054.
Frequency Limit
• You can set both the upper/lower limits to the output frequency.
* To switch to the 2nd/3rd control, allocate 08 (SET)/17 (SET3) to the desired multi-function input and then turn it
on.
• Does not accept any frequency reference beyond the upper/lower limits.
• Set the upper limit first. Make sure that the upper limit (A061/A261) is larger than the lower limit
(A062/A262).
(Example 7-a)
(Example 7-b)
ON
RUN
command
A052
Frequency
reference
Output
frequency
ON
RUN
command
A052
Frequency
reference
Output
frequency
(a) Edge operation
(b) Level operation
ON
RUN
command
A052
Frequency
reference
Output
frequency
A053
ON
RUN
command
A052
Frequency
reference
Output
frequency
Parameter No.
Function name
Data
Default setting
Unit
A061
Frequency upper limit
0.0/Frequency lower limit [A062] to
Max. frequency [A004]
0.0
Hz
A261
*2nd frequency upper limit
0.0/2nd frequency lower limit [A262]
to 2nd max. frequency [A204]
0.0
A062
Frequency lower limit
0.0/Starting frequency to Frequency
upper limit [A061]
0.0
A262
*2nd frequency lower limit
0.0/Starting frequency to 2nd
frequency upper limit [A261]
0.0
Related functions
C001 to C008
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......