4-184
4-4 Communication Function
4
Functions
1264h
PID feedback selection
A076
R/W
0: Input FI
1: Input FV
2: RS485 communication
3: Pulse train frequency
10: Operation function output
⎯
1265h
Reverse PID function
A077
R/W
0: Disabled
1: Enabled
⎯
1266h
PID output limit function
A078
R/W
0 to 1000
0.1 [s]
1267h
PID feedforward selection
A079
R/W
0: Disabled
1: Input FV
2: Input FI
3: Input FE
⎯
1268h
Not used
⎯
⎯
⎯
1269h
AVR selection
A081
R/W
0: Always ON
1: Always OFF
2: OFF during deceleration
⎯
126Ah
AVR voltage selection
A082
R/W
200-V class: 0 (200)
1 (215)
2 (220)
3 (230)
4 (240)
400-V class: 5 (380)
6 (400)
7 (415)
8 (440)
9 (460)
10 (480)
⎯
126Bh
Not used
⎯
⎯
⎯
126Ch
Not used
⎯
⎯
⎯
126Dh
RUN mode selection
A085
R/W
0: Normal operation
1: Energy-saving operation
2: Automatic operation
⎯
126Eh
Energy-saving response/
accuracy adjustment
A086
R/W
0 to 1000
0.1 [%]
126Fh
to
1273h
Not used
⎯
⎯
⎯
1274h
Acceleration time 2
A092
(HIGH)
R/W
1 to 360000
0.01 [s]
1275h
A092
(LOW)
R/W
1276h
Deceleration time 2
A093
(HIGH)
R/W
1 to 360000
0.01 [s]
1277h
A093
(LOW)
R/W
1278h
2-step acceleration/
deceleration selection
A094
R/W
0: Switched via terminal 2CH
1: Switched by setting
⎯
Register
No.
Function name
Function
code
R/W
Monitor and setting parameters
Resolution
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...