4-4 Communication Function
4
Func
tions
<Holding Register Number List (Frequency Reference and Trip Monitor)>
Register
No.
Function name
Function
code
R/W
Monitor and setting parameters
Resolution
0001h
Output frequency setting/monitor
F001
(HIGH)
R/W
0 to 40000
(Enabled when A001 = 03)
0.01
[Hz]
0002h
F001
(LOW)
R/W
0003h
Inverter status A
⎯
R
0: Initial status
1:
⎯
2: Stop
3: RUN
4: Free-run stop
5: Jogging
6: DC injection braking
7: Retry
8: Trip
9: During UV
⎯
0004h
Inverter status B
⎯
R
0: During stop
1: During RUN
2: During trip
⎯
0005h
Inverter status C
⎯
R
0:
⎯
1: Stop
2: Deceleration
3: Constant speed
4: Acceleration
5: Forward
6: Reverse
7: Forward to reverse
8: Reverse to forward
9: Forward run start
10: Reverse run start
⎯
0006h
PID feedback
⎯
R/W
0 to 10000
0.01
[%]
0007h
to
0010h
Not used
⎯
⎯
⎯
0011h
Fault frequency monitor
d080
R
0 to 65530
1 [time]
Note 1: The Inverter's rated current is "1000".
Note 2: If the set value is "10000" (100.0 sec) or more, the value in the second decimal place is ignored.
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......