6-6
6-1 Inspection and Maintenance
6
Inspection and Mai
n
tenance
Motor
General
Check that there
are no abnormal
vibrations or
sounds.
{
Acoustic, feeling, and/
or visual inspection
No faults
Check that there
are no abnormal
odors.
{
Check that there is no
abnormal odor
caused by damage or
overheating.
No faults
Insulation
resistance
Megger check
(Between the
collective motor
terminals and
ground terminal)
{
Disconnect Inverter
main circuit terminals
U/T1, V/T2, and
W/T3, and short-
circuit the 3-phase
motor wires. Then,
use a megger to
measure the
resistance between
the motor wire and
ground terminal.
5 M
Ω
min.
500 V DC
megger
Inspection
part
Inspection
item
Inspection point
Inspection period
Inspection method
Criteria
Meter
Daily
Periodic
1 year 2 years
*1. The life of the smoothing capacitor depends on ambient temperatures.
Refer to "Appendix-2 Product Life Curve" for the replacement reference.
*2. The life of the cooling fan varies depending on the environmental conditions, such as ambient temperature
and/or dust. Check the operation through daily inspections.
*3. The replacement reference (year/cycle) or "
Appendix-2 Product Life Curve
" is based on the expected design
life, which is not guaranteed.
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......