4-155
4-4 Communication Function
4
Func
tions
• Response frame
Positive response: Refer to page 4-155.
Negative response: Refer to page 4-155.
<Command 0B>
Re-calculates internal parameters.
Recalculation is required when the base frequency and H*** parameters are changed via RS485
communication.
• Transmission frame
• Response frame
Positive response: Refer to page 4-155.
Negative response: Refer to page 4-155.
Positive/Negative Responses
<Positive Response>
• Response frame
Frame format
STX
Station No.
Command
BCC
CR
Description
Data size
Setting
STX
Control code (Start of TeXt)
1 byte
STX (0x02)
Station No.
Station No. of the target Inverter
2 bytes
01 to 32
Command
Transmission command
2 bytes
0B
BCC
Block check code
2 bytes
Exclusive OR from station No. to
data. (Refer to page 4-157.)
CR
Control code (Carriage Return)
1 byte
CR (0x0D)
Frame format
STX
Station No.
ACK
BCC
CR
Description
Data size
Setting
STX
Control code (Start of TeXt)
1 byte
STX (0x02)
Station No.
Station No. of the target Inverter
2 bytes
01 to 32
ACK
Control code (ACKnowledge)
1 byte
ACK (0x06)
BCC
Block check code
2 bytes
Exclusive OR from station No. to
data. (Refer to page 4-157.)
CR
Control code (Carriage Return)
1 byte
CR (0x0D)
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......