4-186
4-4 Communication Function
4
Functions
1293h
to
12A4h
Not used
⎯
⎯
⎯
12A5h
Acceleration curve
parameter
A131
R/W
1: Small curve to 10: Large curve
⎯
12A6h
Deceleration curve
parameter
A132
R/W
1: Small curve to 10: Large curve
⎯
12A7h
to
12AEh
Not used
⎯
⎯
⎯
12AFh
Operation frequency input
A setting
A141
R/W
0: Digital Operator (F001)
1: Digital Operator (FREQ adjuster)
2: Input FV
3: Input FI
4: RS485 communication
5: Option 1
6: Option 2
7: Pulse train frequency
⎯
12B0h
Operation frequency input
B setting
A142
R/W
0: Digital Operator (F001)
1: Digital Operator (FREQ adjuster)
2: Input FV
3: Input FI
4: RS485 communication
5: Option 1
6: Option 2
7: Pulse train frequency
⎯
12B1h
Operator selection
A143
R/W
0: Addition (A + B)
1: Subtraction (A - B)
2: Multiplication (A × B)
⎯
12B2h
Not used
⎯
⎯
⎯
12B3h
Frequency addition
amount
A145
(HIGH)
R/W
0 to 40000
0.01 [Hz]
12B4h
A145
(LOW)
R/W
12B5h
Frequency addition
direction
A146
R/W
0: Frequency ref A145
1: Frequency reference - A145
⎯
12B6h
to
12B8h
Not used
⎯
⎯
⎯
12B9h
EL-S-curve ratio 1 during
acceleration
A150
R/W
0 to 50
1 [%]
12BAh
EL-S-curve ratio 2 during
acceleration
A151
R/W
0 to 50
1 [%]
12BBh
EL-S-curve ratio 1 during
deceleration
A152
R/W
0 to 50
1 [%]
12BCh
EL-S-curve ratio 2 during
deceleration
A153
R/W
0 to 50
1 [%]
Register
No.
Function name
Function
code
R/W
Monitor and setting parameters
Resolution
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......