4-2 Function Mode
4
Functions
•With a machine (e.g. lift, ball screw) whose motor shaft rotation is limited, the machine may
be damaged if the allowable rotation limit is exceeded. In this case, set H001 to "01" (auto-
tuning without motor rotation).
•With a motor whose no-load current is unknown, measure the current at 50 Hz in the "V/f
setting" mode, and perform auto-tuning after setting the current value in H023/H223.
•Even if "01" (auto-tuning without motor rotation) is selected in H001, the motor may slightly
rotate.
•To perform auto-tuning for one rank lower motor size, enable the overload limit function and set
the overload limit level to 1.5 times the rated current of the motor.
Operating Procedure
(1) Set auto-tuning selection H001 to "01" or "02".
(2) Turn on the RUN command.
Turning on the RUN command starts automatic operation in the following sequence.
Note 1: When "auto-tuning without motor rotation" is selected (H001 = 01), steps (4) and (5) are not
performed.
Note 2: The rotation frequency in step (5) is defined as follows ("T" is whichever larger value of
acceleration time or deceleration time in step (4)):
When T
≤
0
<
50 s,
x = 40%
When 50 s
≤
T
<
100 s,
x = 20%
When 100 s
≤
T,
x = 10%
Note 3: The auto-tuning result is displayed as follows:
If auto-tuning abnormally ends, perform it again.
(Press the STOP/RESET key to clear the display.)
Note 4: If a trip occurs during auto-tuning, the auto-tuning processing is forced to stop.
(No error message appears. Trip display is given higher priority.)
After removing the cause of a trip, perform the auto-tuning again.
Note 5: If the auto-tuning is interrupted by STOP command input (by pressing the STOP key or by
turning off the RUN command), the parameters for auto-tuning may remain in the Inverter.
To perform the auto-tuning again, initialize the parameters, and then set each parameter
again. (This also applies when you restart ordinary operation.)
Note 6: If the offline auto-tuning is performed with "free V/f setting" selected as the control method,
the Inverter displays an error message and stops processing.
Note 7: Even if auto-tuning is completed normally, the Inverter cannot be operated with the tuning
data. To do so, be sure to set motor parameter selection H002 to "01".
(1) 1st AC excitation (Motor does not run.)
↓
(2) 2nd AC excitation (Motor does not run.)
↓
(3) 1st DC excitation (Motor does not run.)
↓
(4) V/f operation (Motor accelerates up to 80% of the base frequency.)
↓
(5) SLV operation (Motor accelerates up to x% of the base frequency.)
↓
(6) 2nd DC excitation (Motor does not run.)
↓
(7) The auto-tuning result is displayed.
_k_k_ko
Normal end
_k_k_kz
Abnormal end
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......