4-17
4-2 Function Mode
4
Func
tions
Binary Operation
• By allocating 02 to 05 (CF1 to CF4) to any of multi-function inputs 1 to 8 (C001 to C008), you can
select from multi-step speeds 0 to 15.
• Use A021 to A035 (multi-step speeds 1 to 15) to set frequencies for speeds 1 to 15.
• When the Digital Operator is selected as the frequency reference, speed 0 is set with A020/A220/
A320 or F001 (refer to page 4-8). When the control circuit terminal block is selected, speed 0 is set
with terminals FV, FE, and FI.
• For multi-step speed binary operation, you can set the wait time until which the terminal input is
determined in multi-step speed/position determination time C169. This prevents the transition status
before the input determination from being applied.
• If no input is made after the time set in C169, the data is determined.
(Note that the longer the determination time, the slower the input response.)
Multi-step speeds
CF4
CF3
CF2
CF1
0th
OFF
OFF
OFF
OFF
1st
ON
2nd
OFF
OFF
3rd
ON
4th
ON
OFF
OFF
5th
ON
6th
OFF
OFF
7th
ON
8th
ON
OFF
OFF
OFF
9th
ON
10th
OFF
OFF
11th
ON
12th
OFF
OFF
OFF
13th
ON
14th
OFF
OFF
15th
ON
CF1
CF2
CF3
CF4
FW
1st
2nd
3rd
4th
5th
6th
7th
8th
9th
10th
11th
12th
13th
14th
15th
0th
Frequency from
the Digital Operator
or the external
analog input terminal
Determination
time (C169)
CF1
CF2
CF3
Frequency reference
13
1
5
9
Without determination time (C169)
11
CF4
15
With determination time (C169)
4
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......