• To raise the carrier frequency, reduce the output current (or derate the rated current) as shown in
the graph below.
Voltage
200-V class
400-V class
Capacity
Max. fc (kHz)
Derating at fc = 15 kHz
Max. fc (kHz)
Derating at fc = 15 kHz
(75 to 132 kW is for 10 kHz)
0.4 kW
15
100%
15
100%
0.75 kW
15
100%
15
100%
1.5 kW
15
100%
15
100%
2.2 kW
15
100%
15
100%
3.7 kW
15
100%
15
100%
5.5 kW
15
100%
15
100%
7.5 kW
15
100%
15
100%
11 kW
12
90% (41.4 max.)
15
100%
15 kW
12
95% (60.8 A max.)
14
95% (30.4 A max.)
18.5 kW
10
90% (68.4 A max.)
10
90% (34.2 A max.)
22 kW
7
70% (66.5 A max.)
6
75% (36.0 A max.)
30 kW
5
80% (96.8 A max.)
10
75% (43.5 A max.)
37 kW
10
75% (108.7 A max.)
8
80% (60.0 A max.)
45 kW
5
70% (127.4 A max.)
9
75% (68.2 A max.)
55 kW
5
70% (154 A max.)
6
60% (67.2 A max.)
75 kW
⎯
⎯
6
85% (126.7 A max.)
90 kW
⎯
⎯
4
75% (132.0 A max.)
110 kW
⎯
⎯
6
70% (151.9 A max.)
132 kW
⎯
⎯
3
60% (156.0 A max.)
60
55
100
95
90
85
80
75
70
65
0.5 2
4
6
8
10
12
15
14
60
55
100
95
90
85
80
75
70
65
0.5 2
4
6
8
10
12
15
14
200-V class
400-V class
Output current der
ating
Carrier frequency (kHz)
Output current der
ating
Carrier frequency (kHz)
15 kW
37 kW
30 kW
11 kW
18.5 kW
22 kW
45, 55 kW
15 kW
22 kW
132 kW
110 kW
18.5 kW
37 kW
55 kW
30 kW
45 kW
75 kW
90 kW
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......