4-148
4-4 Communication Function
4
Functions
* Each monitor value
Monitor item
Unit
Magnification
Data size
Description
Output frequency
Hz
× 100
8 bytes
Decimal ASCII code
→
MSB
LSB
←
Output current
A
× 10
8 bytes
Decimal ASCII code
Rotation direction
⎯
⎯
8 bytes
0: Stop, 1: Forward,
2: Reverse
PID feedback monitor
%
× 100
8 bytes
Decimal ASCII code
Multi-function input
monitor
⎯
⎯
8 bytes
See
*1
.
Multi-function output
monitor
⎯
⎯
8 bytes
See
*2
.
Frequency conversion
monitor
⎯
× 100
8 bytes
Decimal ASCII code
Output torque
%
× 1
8 bytes
Decimal ASCII code
Output voltage monitor
V
× 10
8 bytes
Decimal ASCII code
Power monitor
kW
× 10
8 bytes
Decimal ASCII code
⎯
⎯
⎯
8 bytes
"00000000" is stored.
(Preliminary data storage
area)
RUN time monitor
h
× 1
8 bytes
Decimal ASCII code
ON time monitor
h
× 1
8 bytes
Decimal ASCII code
*1. Multi-function input terminal monitor
*2. Multi-function output terminal monitor
Item
Data
Item
Data
S1 terminal
00000001
P1 terminal
00000001
S2 terminal
00000002
P2 terminal
00000002
S3 terminal
00000004
P3 terminal
00000004
S4 terminal
00000008
P4 terminal
00000008
S5 terminal
00000010
P5 terminal
00000010
S6 terminal
00000020
Relay terminal
00000020
S7 terminal
00000040
S8 terminal
00000080
FW terminal
00000100
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......