4-3
4-1 Monitor Mode
4
Func
tions
Note: When the frequency reference is set using the Digital Operator, the output frequency can be
changed with the Increment/Decrement key during operation only.
The frequency setting changed with this monitor will be reflected in frequency reference F001.
Pressing the Enter key overwrites the currently selected frequency reference. (The data
storage accuracy depends on each frequency reference.)
Real Frequency Monitor [d008]
When a motor with an encoder is connected to a load, and the PG board (3G3AX-PG01) is used,
this monitor displays the real frequency of the motor (regardless of the control method).
(Display)
In forward rotation: 0.00 to 99.99
: Displays in increments of 0.01 Hz.
100.0 to 400.0 : Displays in increments of 0.1 Hz.
In reverse rotation: -0.0 to -99.9
: Displays in increments of 0.1 Hz.
-100 to -400
: Displays in increments of 1 Hz.
Note 1: To use this monitor, set the number of encoder pulses (P011) and the motor pole number
selection (H004 or H204) correctly.
Note 2: The monitored value does not depend on V/f characteristics selection A044.
Torque Reference Monitor [d009]
When torque control is selected for sensor vector control, this monitor displays the currently entered
torque reference value.
The data LED indicator "%" lights up while the d009 setting is displayed.
(Display)
0. to 200.: Displays in increments of 1%.
Torque Bias Monitor [d010]
When sensor vector control is selected, this monitor displays the torque bias amount currently set
in display code d010.
The data LED indicator "%" lights up while the d010 setting is displayed.
(Display)
-150. to +150.: Displays in increments of 1%.
Output Torque Monitor [d012]
Displays an estimated value of the Inverter's output torque.
The data LED indicator "%" lights up while the d012 setting is displayed.
(Display)
-300. to +300.: Displays in increments of 1%.
Note: This monitor is enabled only when "sensorless vector control", "0-Hz sensorless vector
control" , or "sensor vector control" is selected as the control mode.
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......