4-40
4-2 Function Mode
4
Functions
Pattern Curve Parameter (Curve Factor)
• Determine a curve factor with reference to the figures below.
• The S pattern has an intermediate section where acceleration/deceleration time is shortened.
• If LAD cancel (LAC) is selected for a multi-function input and that input is turned on, the
acceleration/deceleration pattern is ignored, and the output frequency instantaneously follows the
reference frequency.
EL-S Curve Ratio
If the EL-S pattern is used, you can set a curve ratio (A151 to A153) individually for acceleration and
deceleration.
If all settings are "50 (%)", the Inverter operates in the same manner as with the S curve.
Output frequency (Hz)
Output frequency (Hz)
Output frequency (Hz)
Target
frequency
(100%)
Target
frequency
(100%)
Target
frequency
(100%)
96.9
82.4
17.6
3.1
02
25
50
75
10
10
02
Time
Acceleration time before reaching the
output frequency set value (100%)
99.6
93.8
87.5
68.4
64.6
35
25
50
75
Time
Acceleration time before reaching the
output frequency set value (100%)
65
35.4
31.6
12.5
6.25
0.39
25
50
75
Time
Acceleration time before reaching the
output frequency set value (100%)
10
02
10
10
02
Output frequency ratio (%)
100
50
Curve ratio 2 during
acceleration (A151)
Curve ratio 1 during
acceleration (A150)
Curve ratio 1 during
deceleration (A152)
Curve ratio 2 during
deceleration (A153)
Time(s)
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......