3-35
3-7 Parameter List
3
Operation
Others
b046
Reverse rotation
prevention selection
00: Disabled
01: Enabled
00
No
Yes
⎯
b050
Selection of non-stop
function at
momentary power
interruption
00: Disabled
01: Enabled (deceleration stop)
02: Enabled (without recovery)
03: Enabled (with recovery)
00
No
No
⎯
b051
Starting voltage of
non-stop function at
momentary power
interruption
0.0 to 999.9
1000.
220/
440
No
No
V
b052
Stop deceleration
level of non-stop
function at
momentary power
interruption
0.0 to 999.9
1000.
360/
720
No
No
V
b053
Deceleration time of
non-stop function at
momentary power
interruption
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
1.00
No
No
s
b054
Deceleration starting
width of non-stop
function at
momentary power
interruption
0.00 to 10.00
0.00
No
No
Hz
b055
Proportional gain
setting of non-stop
function at
momentary power
interruption
0.00 to 2.55
0.20
Yes
Yes
⎯
b056
Integral time setting
of non-stop function
at momentary power
interruption
0.000 to 9.999/10.00 to 65.53
0.100
Yes
Yes
s
Parameter
No.
Function name
Monitor or data range
Default
setting
Changes during
operation
Unit
Page
Normal b031 = 10
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......