App-15
Appendix-1 Parameter List
Appe
ndix
Lo
ck
b031
Soft lock selection
00: Data other than b031 cannot be changed
when terminal SFT is ON.
01: Data other than b031 and the specified
frequency parameter cannot be changed
when terminal SFT is ON.
02: Data other than b031 cannot be
changed.
03: Data other than b031 and the specified
frequency parameter cannot be
changed.
10: Data can be changed during RUN.
01
No
Yes
⎯
Others
b034
RUN time/Power ON
time setting
0. to 9999. (0 to 99990)
1000 to 6553 (100000 to 655300)
0.
No
Yes
h
b035
Rotation direction
limit selection
00: Forward and Reverse are enabled
01: Only Forward is enabled.
02: Only Reverse is enabled.
00
No
No
⎯
b036
Reduced voltage
startup selection
0 (Reduced voltage startup time: small) to
255 (Reduced voltage startup time: large)
6
No
Yes
⎯
b037
Display selection
00: Complete display
01: Individual display of functions
02: User setting
03: Data comparison display
04: Basic display
04
No
Yes
⎯
b038
Initial screen
selection
00: Screen when the Enter key was pressed
last
01: d001
02: d002
03: d003
04: d007
05: F001
01
No
Yes
⎯
b039
User parameter
automatic setting
function selection
00: Disabled
01: Enabled
00
No
Yes
⎯
Parameter
No.
Function name
Monitor or data range
Default
setting
Changes during
operation
Unit
Page
Normal b031 = 10
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......