4-51
4-2 Function Mode
4
Func
tions
Overcurrent Suppression Function
• This function suppresses overcurrent caused by a steep current rise in rapid acceleration.
• You can set whether to enable or disable this function with b027.
Note: If you use the Inverter with an elevating machine, disable this function.
Otherwise, the machine may slide down.
Soft Lock Function
• You can set whether to enable or disable the writing of various code data.
This helps prevent data rewriting due to erroneous operation.
• Select the soft lock setting and performing method from the above table.
• To use a multi-function input terminal, allocate 15 (SFT) to any of multi-function inputs 1 to 8 (C001
to C008).
Parameter No.
Function name
Data
Default setting
Unit
b027
Overcurrent suppression
function
00: Disabled
01: Enabled
01
⎯
Output frequency
Desired
Actual acceleration after
suppression operation
Time
Output current
Time
Suppression level
(about 160% of the rating)
Parameter No.
Function name
Data
Default setting
Unit
b031
Soft lock selection
00: Data other than b031 cannot be changed
when terminal SFT is ON.
01: Data other than b031 and specified frequency
parameter cannot be changed when terminal
SFT is ON.
02: Data other than b031 cannot be changed.
03: Data other than b031 and specified frequency
parameter cannot be changed.
10: Data can be changed during RUN.
01
⎯
Related functions
C001 to C008, SFT input
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......