ILBLP CP HE SD HV

“S” MOUNTING STYLE

CONSTANT POWER 

 EMERGENCY LIGHTING EQUIPMENT 

FOR LED

(800) 866-4682  •  www.iotaengineering.com

INSTRUCTION MANUAL

HIGH EFFICIENCY PERFORMANCE 

MEETS CA T20 BATTERY CHARGER 

EFFICIENCY STANDARDS

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be followed, including the following:

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

 1. 

CAUTION 

– The TBTS Test Button Component serves as the unit connector.  The 

ILBLP CP HE SD HV

 will 

initiate

 

once both the TBTS until installation is complete and A.C. power is supplied to the unit.

 2. 

CAUTION 

– This fixture provides more than one power supply output source. To reduce the risk of electrical 

shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by discon

-

necting the TBTS Test Button Component before servicing.

 3. 

CAUTION 

– This equipment provides reduced current levels when higher voltage loads are connected. Load 

calibration is required to ensure proper operation (see page 4).

 4. 

CAUTION 

– This is a sealed unit. Components are not replaceable. Replace the entire unit when necessary.

 5. 

CAUTION

 – Installation and servicing should be performed by 

qualified personnel only

. De-energize before 

opening.

 6.  The 

ILBLP CP HE SD HV

 is for use with grounded LED luminaires listed to UL standards. Not for use in 

heated air outlets or hazardous locations.

 7. 

The 

ILBLP CP HE SD HV

 and A.C. driver 

must 

be on the same branch circuit.

  8.  Do not mount near gas or electric heaters.
 9.  The 

ILBLP CP HE SD HV

 should be mounted in locations and at heights where it will not readily be subjected 

to tampering by unauthorized personnel.

 10.  Product output voltage varies according to wattage. Refer to 

Illustration 1 

for output voltage per model.

11.   The 

ILBLP CP HE SD HV 

is certified in the CA Title 20 Modernized Appliance Efficiency Database System 

(MAEDBS) as a small battery charger.

 12.  Suitable for use in damp locations.

 13.  For use in 0° C minimum, 55° C maximum ambient temperatures.

 14.  The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition, void 

warranty, and result in non-compliance with UL specifications.

 15.  Do not use this equipment for other than intended use.
 16.  Install in accordance with the National Electrical Code and local regulations.

17.  Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before 

final installation. See addendum for compatibility and covered luminaire requirements.

SAVE THESE  INSTRUCTIONS

Summary of Contents for ILBLP CP10 HE SD

Page 1: ...should be performed by qualified personnel only De energize before opening 6 The ILBLP CP HE SD HV is for use with grounded LED luminaires listed to UL standards Not for use in heated air outlets or hazardous locations 7 The ILBLP CP HE SD HV and A C driver must be on the same branch circuit 8 Do not mount near gas or electric heaters 9 The ILBLP CP HE SD HV should be mounted in locations and at h...

Page 2: ...erly seated in the TBTS Socket then mark the TBTS location on the switch box plate with the TBTS Label and apply the SD Status Indicator Sticker FLEX CEILING TILE LED DRIVER AND ARRAY COMPARTMENT TBTS Lorem ipsum TBTS ILBLP CP HE SD HV LUMINAIRE HOUSING L U M I N A I R E H O U S I N G T B T S N U T TBTS NUT Remote Mounting The TBTS may be remote mounted from the fixture up to 25 feet Before extend...

Page 3: ...d allow the unit to charge for at least 1 hour before performing a functional test B Verify that the TBTS light is on The lamp will illuminate Red while the battery is charging and Green when the battery is fully charged C Press and hold the TBTS button for two seconds The pilot light will blink Within five seconds the LED Module should be operating at a reduced light output The test mode runs for...

Page 4: ...r inspection by the authority having jurisdiction SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL Consult Customer Service or visit www iotaengineering com for current warranty information Load Calibration To ensure proper operation Load Calibration is required whenever the LED load connected to the ILBLP CP HE SD HV is changed Note Load Calibration happens automatically 48 hours after the IL...

Page 5: ... CP HE SD HV est conçu pour être utilisé avec des luminaires à DEL mis à la terre homologués UL Ne pas utiliser avec des prises d air chauffées ou dans des endroits dangereux 7 Le pilote ILBLP CP HE SD HV et c a doit être sur le même circuit de dérivation 8 Ne pas installer à proximité d appareils de chauffage au gaz ou électriques 9 L ILBLP CP HE SD HV doit être installé à des endroits et à des h...

Page 6: ...rges LED haute tension non classe 2 Voir l illustration 1 pour les tensions nominales de sortie par modèle ILBLP ÉTAPE 3 INSTALLER LE COMMUTATEUR DE TEST DU CORPS FILETÉ TBTS A Trouvez un emplacement satisfaisant pour la TBTS et le câble qui est visible à l extérieur du luminaire Percez ou défoncez un trou d un diamètre de 1 2 po dans la paroi du luminaire ou dans le couvercle du chemin de câbles ...

Page 7: ... alimentation secteur fait fonctionner le module DEL comme prévu L ILBLP CP HE SD HV est en mode de chargement en veille Le TBTS est allumé et indique de manière visuelle que la batterie est en cours de chargement Mode d urgence L alimentation secteur tombe en panne L ILBLP CP HE SD HV détecte la panne de courant et bascule automatiquement en mode d urgence Le module DEL est allumé et la sortie es...

Page 8: ...inq secondes jusqu à ce que le module à DEL s éteigne Méthode 2 Débranchez le TBTS Une fois que toutes les sources d alimentation sont débranchées du luminaire ILBLP CP HE SD HV et du luminaire d urgence procéder à l entretien requis Une fois l entretien terminé rebrancher le TBTS si débranché et rétablir l alimentation c a au luminaire d urgence Le circuit AC Activate détectera la présence d une ...

Reviews: