background image

                                                                                                                   

VM600

 

 

- 0 - 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

VM600  AC  Drive 

User Manual 

 

Verion  Code  6.0004.0538-00-VM600-E-V03-202107 

 

Summary of Contents for VM600

Page 1: ...VM600 0 VM600 AC Drive User Manual Verion Code 6 0004 0538 00 VM600 E V03 202107...

Page 2: ...f the labor supervision department and the electrical and environmental conditions for product use shall be in conformity with relevant national standards Be sure to verify that the wiring is correct...

Page 3: ...ON 10 CHAPTER 3 DISPLAY AND OPERATION 12 3 1 KEYPAD 12 3 2 DESCRIPTION OF INDICATORS AND KEYS 12 CHAPTER 4 PARAMETER FUNCTION 13 4 1 FUNCTIONAL PARAMETER 13 4 2 MONITORING PARAMETERS 20 4 3 ERROR RECO...

Page 4: ...vironment Otherwise fire may be caused When AC Drive is installed inside an electrical cabinet or other kind of enclosure please install fans or other cooling devices and keep ventilation well enough...

Page 5: ...static electricity will damage the PCB board DANGER Wiring must be completed by qualified professional electricians otherwise there may be electric shock or damage to the AC Drive The power must be d...

Page 6: ...Never touch the AC Drive connection terminals when power is on Otherwise it may cause an electrical shock Only qualified electricians can be authorized to do the jobs of maintenance checking or parts...

Page 7: ...source such as digital setting analog voltage setting analog current setting serial communication port setting DC braking Braking time 0 0s 50 0s Braking action current value 0 0 100 0 Simple PLC Mul...

Page 8: ...eplate IP20 Product model Power Input specification Output specification Product barcode Certification protection level MODEL VM600 2S1R5 E POWER 1 5kW INPUT 1PH AC 220V 15 14A 50 60Hz OUTPUT 3PH AC 0...

Page 9: ...1 VM600 2S1R5 1 5 3 14 2 7 1 5 2 VM600 2S2R2 2 2 4 23 9 6 2 2 3 VM600 4TR75 0 75 1 5 3 4 2 5 0 75 1 VM600 4T1R5 1 5 3 5 3 8 1 5 2 VM600 4T2R2 2 2 4 5 8 5 1 2 2 3 VM600 4T004 4 5 9 10 5 9 4 5 5 VM600...

Page 10: ...rive Model Overall Dimensions Mounting Hole Mounting Hole Diameter H W D H1 W1 d VM600 2SR75 134 69 104 123 55 5 VM600 2S1R5 VM600 2S2R2 142 72 116 130 59 5 VM600 4TR75 VM600 4T1R5 VM600 4T2R2 VM600 4...

Page 11: ...DI3 DI4 Forward Reverse Fault reseting Multi speed terminal 1 RC RA Relay output S S RS485 communication terminal I AI V R L S T N U V W PE MCCB Power input terminal L1 L2 L3 Out ternimal PE RJ45 Ana...

Page 12: ...Function description Power supply 10V GND 10V power supply Provide 10V power supply to external unit Maximum output current 20 mA 24V COM 24V power supply Provide 24V power supply to external unit Ana...

Page 13: ...inking Forward and reverse switching ALARM Blinking Fault state PRG Programming Enter or exit the first menu ENT Confirm Enter the menu interfaces and confirm the parameter setting Increment Increase...

Page 14: ...0 Digital setting non retentive at power failure 1 Digital setting retentive at power failure 2 Keypad Knob 3 AI 4 Multi stage speed 5 Simple PLC 6 Communication 2 0002 F0 03 Keypad setting frequency...

Page 15: ...0 0102 F2 00 Motor Rated Power 0 1kW 2 2kW Determined by Drive Model 0200 F2 01 Motor Rated Voltage 0 380V Determined by Drive Model 0201 F2 02 Motor Rated Frequency 0 F0 05 Determined by Drive Model...

Page 16: ...rward point movement FJOG 5 Reverse point movement RJOG 6 Error Reset 7 Terminal UP 8 Terminal Down 9 UP DOWN Setting Clear 10 External error input Normally Open 11 PLC Status reset 12 Multi stage spe...

Page 17: ...d Level Option 0 Low Level Valid 1 High Level Valid 1 0511 F6 00 Relay Output Option 0 No Output 1 VFD Running 2 Error Output Output is valid only after VFD stops 3 Ready for Running 4 Communication S...

Page 18: ...00 1 00 060D F7 00 Reserved Reserved 0 0700 F7 01 STOP Button Function 0 Valid only at keypad control mode 1 Valid at all control modes 1 0701 F7 02 LED display parameters at running status Bit0 Runn...

Page 19: ...0D00 FD 01 Multistage speed 1 100 0 100 0 0 00 0D01 FD 02 Multistage speed 2 100 0 100 0 0 00 0D02 FD 03 Multistage speed 3 100 0 100 0 0 00 0D03 FD 04 Simple PLC running mode 0 Stop after the AC Driv...

Page 20: ...fault Property Address FD 13 Acceleration deceleration time of simple PLC reference 3 0 3 0 0D0D FD 14 Time unit of simple PLC running 0 s second 1 h hour 2 min minute 0 0D0E FD 15 The source of multi...

Page 21: ...001 D0 02 Bus Voltage V 0 1V D002 D0 03 Output Voltage V 1V D003 D0 04 Output Current A 0 01A D004 D0 05 IGBT Module Temperature 0 1 D005 D0 06 DI Input Status 1 D006 D0 07 DO Output Status 1 D007 D0...

Page 22: ...r18 Parameter writing reading error Err21 EEPROM writing reading error Err22 E000 E0 01 Running Frequency at latest error 0 0Hz F0 05 E001 E0 02 Output Current at latest error 0 00 655 35 E002 E0 03 B...

Page 23: ...0007 Fault reset W Running Status 3000H 0001 FWD running R 0002 REV running R 0003 Stopped R Monitoring Data 1001H Running Frequency Hz 2 decimal places R 1002H Set Frequency Hz 2 decimal places R 100...

Page 24: ...r off and does not save it In the communication mode for the write command 06H if the parameter needs to be stored after power off the method of writing EEPROM should be used The original 0 of the mos...

Page 25: ...ternal force 3 Increase the acceleration time 4 Installed the braking unit and braking resistor Err06 Overvoltage during deceleration 1 Input voltage abnormal 2 An external force drives the motor duri...

Page 26: ...nication cable is faulty 3 The communication parameters of FC group are set improperly 1 Check the cabling of the PC 2 Check the communication cabling 3 Set the communication parameters properly Err18...

Page 27: ...d is abnormal 1 Check and reset the parameters in group F5 2 Re connect the external signal cables 3 Ask for technical service 4 AC Drive interference 1 Carrier frequency setting is not suitable 2 The...

Page 28: ...City Guangzhou High tech Zone Guangdong P R China Postcode 510663 Web http www saj electric com Technical Support Service Fax 86 20 6660 8589 E mail service drive01 saj electric com International Sal...

Page 29: ...anty Card Customer info Company name Company address Contact Tel Fax Zip code Product info Product model SN code Buying date Fault date Motor power Application situation Fault info Fault description S...

Page 30: ...VM600 29 Due to continuous improvement of products technical parameters in this manual are modified without prior notice...

Reviews: