Parameters
(E) Environment setting parameters
FR-A800
5 - 229
PWM carrier frequency automatic reduction function (Pr. 260)
●
Setting Pr. 260 = "1 (initial value)" will enable the PWM carrier frequency auto-reduction function.
If a heavy load is continuously applied while the inverter carrier frequency is set to 3 kHz or higher
(Pr. 72
≥
"3"), the carrier frequency is automatically reduced to prevent occurrence of the inverter
overload trip (electronic thermal O/L relay function) (E.THT). The carrier frequency is reduced to
as low as 2 kHz. (Motor noise increases, but not to the point of failure.)
●
When the PWM carrier frequency automatic reduction function is used, the operation with the
carrier frequency set to 3 kHz or higher (Pr. 72
≥
"3") automatically reduces the carrier frequency
for heavy-load operation as shown below.
Pr. 260
setting
Pr. 570
setting
Carrier frequency automatic reduction operation
FR-A820-04750(90K) or lower,
FR-A840-02600(90K) or lower
FR-A840-03250(110K) or higher
1
0 (SLD),
1 (LD)
Continuous operation with the 85% or higher inverter rated current reduces the carrier
frequency automatically.
2 (ND),
3 (HD)
Operation with the 150% or higher inverter
rated current for the ND rating reduces the
carrier frequency automatically.
Continuous operation with the 85% or higher
inverter rated current reduces the carrier
frequency automatically.
0
0 (SLD)
Continuous operation with the 85% or higher inverter rated current reduces the carrier
frequency automatically.
1 (LD)
Without carrier frequency automatic reduction
(Perform continuous operation with the carrier frequency set to 2 kHz or lower or with less than
85% of the inverter rated current.)
2 (ND),
3 (HD)
Without carrier frequency automatic reduction
Without carrier frequency automatic reduction
(Perform continuous operation with the carrier
frequency set to 2 kHz or lower or with less
than 85% of the inverter rated current for the
ND rating.)
Tab. 5-91:
Parameter settings for PWM carrier frequency automatic reduction operation
NOTES
Reducing the PWM carrier frequency is effective as a countermeasure against EMI from the
inverter or for reducing leakage current, but doing so increases the motor noise.
When the PWM carrier frequency is set to 1 kHz or lower (Pr. 72
≤
1), the increase in the harmonic
current causes the fast-response current limit to activate before the stall prevention operation,
which may result in torque shortage. In this case, disable the fast-response current limit in Pr. 156
"Stall prevention operation selection".
The lower limit of carrier frequency after the reduction under PM sensorless vector control (low-
speed range high-torque characteristic enabled) is 6 kHz.
During fast-response operation, the carrier frequency automatic reduction function is disabled.
Parameters referred to
Pr. 156
Stall prevention operation selection
=>
Pr. 570
Multiple rating setting
=>
Pr. 788
Low speed range torque characteristic selection
=>
Pr. 800
Control method selection
=>
Summary of Contents for FR-A820-00046 (0.4K)
Page 2: ......
Page 4: ......
Page 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Page 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Page 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1190: ...EC Declarations of Conformity Appendix A 50 ...
Page 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Page 1192: ...EC Declarations of Conformity Appendix A 52 ...
Page 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1194: ...EC Declarations of Conformity Appendix A 54 ...
Page 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1196: ...EC Declarations of Conformity Appendix A 56 ...
Page 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Page 1198: ...EC Declarations of Conformity Appendix A 58 ...
Page 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Page 1200: ...EC Declarations of Conformity Appendix A 60 ...
Page 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Page 1202: ...EC Declarations of Conformity Appendix A 62 ...
Page 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Page 1204: ...EC Declarations of Conformity Appendix A 64 ...
Page 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Page 1206: ...EC Declarations of Conformity Appendix A 66 ...
Page 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Page 1208: ...EC Declarations of Conformity Appendix A 68 ...
Page 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Page 1210: ...EC Declarations of Conformity Appendix A 70 ...
Page 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Page 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Page 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Page 1214: ...EC Declarations of Conformity Appendix A 74 ...
Page 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Page 1217: ......