(N) Operation via communication and its settings
Parameters
5 - 632
Waiting time setting from the communication line error occurrence to the communication error
activation (Pr. 500)
●
When a communication option is used, use Pr. 500 "Communication error execution waiting time"
to set the time from when the communication line error occurs until the inverter starts the
operation for the communication error.
●
When a communication line error occurs and lasts longer than the time set in Pr. 500, it is
recognized as a communication error. If the communication returns to normal within the time, it
is not recognized as a communication error, and the operation continues.
●
Operation from the error occurrence until the Pr. 500 setting time elapses
When the communication returns to normal within the time period set in Pr. 500, the communi-
cation option error (E.OP1) does not occur.
I002852E
Fig. 5-315:
Recognition of a communication error depending on Pr. 500 setting
Error definition
Pr. 502 setting Operation
Indication
Fault output
Communication line
0
Continued
Not provided
1
2
3
4
CF
Communication option
itself
0, 3
Coast to stop
E. 1 lit
Provided
1, 2
Decelerated to stop
E. 1 lit after stop
Provided after stop
4
Continued
CF
Not provided
Tab. 5-273:
Operation at error occurrence
Normal
Normal
Error
Recognition
ON
Pr. 500
setting time
Communication line status
Communication error (E.OP1)
Alarm signal (LF)
(Pr. 502 = 3 or 4)
Error
Pr. 500
setting time
Summary of Contents for FR-A820-00046 (0.4K)
Page 2: ......
Page 4: ......
Page 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Page 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Page 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1190: ...EC Declarations of Conformity Appendix A 50 ...
Page 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Page 1192: ...EC Declarations of Conformity Appendix A 52 ...
Page 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1194: ...EC Declarations of Conformity Appendix A 54 ...
Page 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1196: ...EC Declarations of Conformity Appendix A 56 ...
Page 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Page 1198: ...EC Declarations of Conformity Appendix A 58 ...
Page 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Page 1200: ...EC Declarations of Conformity Appendix A 60 ...
Page 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Page 1202: ...EC Declarations of Conformity Appendix A 62 ...
Page 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Page 1204: ...EC Declarations of Conformity Appendix A 64 ...
Page 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Page 1206: ...EC Declarations of Conformity Appendix A 66 ...
Page 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Page 1208: ...EC Declarations of Conformity Appendix A 68 ...
Page 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Page 1210: ...EC Declarations of Conformity Appendix A 70 ...
Page 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Page 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Page 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Page 1214: ...EC Declarations of Conformity Appendix A 74 ...
Page 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Page 1217: ......