Parameters
(C) Motor constant parameters
FR-A800
5 - 459
For FR-A820-00077(0.75K) or lower and FR-A840-00038(0.75K) or lower, it is set to 85% of the
inverter rated current.
For the FR-A820-03160(55K) or lower and FR-A840-01800(55K)or lower.
For the FR-A820-03800(75K) or higher and FR-A840-02160(75K)or higher.
Differs according to the voltage class. (200 V/400 V)
$
The setting range and unit change according to the Pr. 71 (Pr. 450) setting.
458
C220
Second motor
constant (R1)
9999
0 to 50 Ω, 9999
Tuning data of the second motor
(The value measured by offline auto tuning
is automatically set.)
9999: Uses the constant value of Mitsubishi
motor (SF-PR, SF-JR, SF-HR, SF-JRCA,
SF-HRCA and so on).
0 to 400 mΩ, 9999
459
C221
Second motor
constant (R2)
9999
0 to 50 Ω, 9999
0 to 400 mΩ, 9999
460
C222
Second motor
constant (L1) / d-axis
inductance (Ld)
9999
0 to 400 mH, 9999
461
C223
Second motor
constant (L2) / q-axis
inductance (Lq)
9999
0 to 6000 mH, 9999
0 to 400 mH, 9999
462
C224
Second motor
constant (X)
9999
0 to 100%, 9999
455
C225
Second motor
excitation current
9999
0 to 500 A, 9999
0 to 3600 A, 9999
860
C226
Second motor
torque current/
Rated PM motor
current
9999
0 to 500 A, 9999
0 to 3600 A, 9999
560
A712
Second frequency
search gain
9999
0 to 32767
The offline auto tuning automatically sets
the gain required for the frequency search
of the second motor.
9999
Uses the constant value of Mitsubishi motor
(SF-PR, SF-JR, SF-HR, SF-JRCA, SF-HRCA and
so on).
NOTES
The function is enabled under Advanced magnetic flux vector control, Real sensorless vector con-
trol, and vector control.
Even if a motor other than Mitsubishi standard motors (SF-JR 0.4 kW or higher), high-efficiency
motors (SF-HR 0.4 kW or higher), Mitsubishi constant-torque motors (SF-JRCA 4P, SF-HRCA 0.4 kW
to 55 kW), Mitsubishi high-performance energy-serving motor (SF-PR), or vector control dedicated
motors (SF-V5RU (1500 r/min series)), such as other manufacturers' induction motors, SF-JRC, SF-
TH, etc., is used, or when the wiring length is long (approx. 30 m or longer), a motor can run with
the optimum operation characteristics by using the offline auto tuning function.
Tuning is enabled even when a load is connected to the motor.
During offline auto tuning, the motor rotation can be locked (Pr. 96 = "1") or unlocked (Pr. 96 =
"101"). The tuning is more accurate when the motor can rotate (unlocked).
Reading/writing of the motor constants tuned by offline auto tuning are enabled. The offline auto
tuning data (motor constants) can be copied to another inverter with the operation panel.
The offline auto tuning status can be monitored with the operation panel and the parameter unit.
Pr.
Name
Initial
value
Setting range
Description
Summary of Contents for FR-A820-00046 (0.4K)
Page 2: ......
Page 4: ......
Page 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Page 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Page 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1190: ...EC Declarations of Conformity Appendix A 50 ...
Page 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Page 1192: ...EC Declarations of Conformity Appendix A 52 ...
Page 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1194: ...EC Declarations of Conformity Appendix A 54 ...
Page 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1196: ...EC Declarations of Conformity Appendix A 56 ...
Page 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Page 1198: ...EC Declarations of Conformity Appendix A 58 ...
Page 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Page 1200: ...EC Declarations of Conformity Appendix A 60 ...
Page 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Page 1202: ...EC Declarations of Conformity Appendix A 62 ...
Page 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Page 1204: ...EC Declarations of Conformity Appendix A 64 ...
Page 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Page 1206: ...EC Declarations of Conformity Appendix A 66 ...
Page 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Page 1208: ...EC Declarations of Conformity Appendix A 68 ...
Page 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Page 1210: ...EC Declarations of Conformity Appendix A 70 ...
Page 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Page 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Page 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Page 1214: ...EC Declarations of Conformity Appendix A 74 ...
Page 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Page 1217: ......