(M) Monitor display and monitor output signal
Parameters
5 - 342
Monitor display (setting) increments
●
When both Pr. 37 and Pr. 144 have been set, their priorities are as given below.
Pr. 144 = 102 to 112 > Pr. 37 = 1 to 9998 > Pr. 144 = 2 to 12
●
The combination of the Pr. 37 and Pr. 144 settings as shown below determines the setting
increment for each monitor. (The initial values are shown in grey shaded fields.)
Motor speed r/min conversion formula:
Frequency ×120 / Number of motor poles (Pr. 144)
Machine speed conversion formula:
Pr. 37 × Frequency / Pr. 505
For Pr. 144 in the above formula, the value is "Pr. 144 – 100" when "102 to 112" is set in Pr. 144; and
the value is "4" when Pr. 37 = 0 and Pr. 144 = 0.
Pr. 505 is always set as frequency (Hz).
Use Pr. 811 to change the increment from 1 r/min to 0.1 r/min.
Pr. 37
Setting
Pr. 144
Setting
Output frequency
monitor
Set frequency monitor
Running speed
monitor
Frequency setting
parameter setting
0
(initial
value)
0
0.01 Hz
0.01 Hz
0.01 Hz
2 to 12
0.01 Hz
0.01 Hz
0.01 Hz
102 to 112
1 r/min
1 r/min
1 r/min
1 to 9998
0
0.01 Hz
0.01 Hz
1 (machine speed
)
0.01 Hz
2 to 12
1 (machine speed
1 (machine speed
)
1 (machine speed
102 to 112
0.01 Hz
0.01 Hz
0.01 Hz
Tab. 5-129:
Setting range of parameter 37 and 144
NOTES
The inverter's output frequency is displayed as synchronous speed under V/F control. The dis-
played value is "actual motor speed" + "motor slip." When Advanced magnetic flux vector control,
Real sensorless vector control or PM sensorless vector control is selected, the actual motor speed
(estimated value by motor slip calculation) is used. When the encoder feedback control or vector
control is selected, the actual motor speed from the encoder is used.
When Pr. 37 = "0" and Pr. 144 = "0", the running speed monitor is displayed with the number of
motor poles 4. (Displays 1800 r/min at 60 Hz)
To change the PU main monitor (PU main display), refer to Pr. 52.
If the setting increment is changed to 1 r/min (Pr. 811 = "0,10") after setting the running speed in
0.1 r/min (Pr. 811 = "1,11"), the 0.1 r/min increment may be dropped, in order for the rotations per
minute resolution to change from 0.1 r/min to 0.3 r/min (when using four poles).
When using the machine speed display for the parameter unit (FR-PU07), do not change the speed
with the up/down key if a set speed above 65535 is being displayed. The set speed may become
an undetermined value.
When the FR-A8ND option is connected, the frequency display (setting) will be used regardless of
the Pr. 37, Pr. 144 settings.
When Pr. 811 = "1 or 11" with the 0.1 r/min increment, the upper limit is as follows.
Speed command setting range: 6000 r/min for 2 to 10 motor poles, 5900 r/min for 12 motor poles
Running speed monitor such as the operation panel: 6553.5 r/min
Full scale of the running speed motor for analog output (terminals FM, CA and AM): 6000 r/min
Summary of Contents for FR-A820-00046 (0.4K)
Page 2: ......
Page 4: ......
Page 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Page 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Page 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1190: ...EC Declarations of Conformity Appendix A 50 ...
Page 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Page 1192: ...EC Declarations of Conformity Appendix A 52 ...
Page 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1194: ...EC Declarations of Conformity Appendix A 54 ...
Page 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1196: ...EC Declarations of Conformity Appendix A 56 ...
Page 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Page 1198: ...EC Declarations of Conformity Appendix A 58 ...
Page 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Page 1200: ...EC Declarations of Conformity Appendix A 60 ...
Page 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Page 1202: ...EC Declarations of Conformity Appendix A 62 ...
Page 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Page 1204: ...EC Declarations of Conformity Appendix A 64 ...
Page 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Page 1206: ...EC Declarations of Conformity Appendix A 66 ...
Page 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Page 1208: ...EC Declarations of Conformity Appendix A 68 ...
Page 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Page 1210: ...EC Declarations of Conformity Appendix A 70 ...
Page 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Page 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Page 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Page 1214: ...EC Declarations of Conformity Appendix A 74 ...
Page 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Page 1217: ......