Parameters
CC-Link IE Field Network (FR-A800-GF)
FR-A800
5 - 753
Torque control cannot be performed with a PM motor.
Input signals to the master module (output signals from the inverter)
RY3A
Error reset request flag
When "1" is set in the error reset request flag (RY3A) at an inverter fault, the inverter is
reset, then "0" is set in the error status flag (RX3A). Refer topage 5-633 for operation
conditions of inverter reset.
Device No.
Signal
Description
RX0
Forward running
0 : Other than forward running (during stop or reverse rotation)
1 : Forward running
RX1
Reverse running
0 : Other than reverse running (during stop or forward rotation)
1 : Reverse running
RX2
Running (terminal RUN function)
앫
Functions assigned to terminals RUN, SU, OL, IPF, FU, ABC1 and ABC2 activate.
앫
Signal names are initial values. Using Pr. 190 to Pr. 196, you can change output
signal functions.
RX3
Up to frequency (terminal SU function)
RX4
Overload alarm (terminal OL function)
RX5
Instantaneous power failure (terminal
IPF function)
RX6
Frequency detection (terminal FU
function)
RX7
Fault (terminal ABC1 function)
RX8
— (terminal ABC2 function)
RX10
— (DO0 function)
앫
Functions assigned to Pr. 313 to Pr. 315 are activated.
앫
No signal is assigned in the initial setting. Use Pr.313 to Pr.315 to assign signals to
the devices RX10 to RX12.
RX11
— (DO1 function)
RX12
— (DO2 function)
RX20
Monitoring
After "1" is set in the monitor command (RY20), and the monitored value is set in the
remote register RWr26 to RWr2F, "1" is set in this signal. When "0" is set in the monitor
command (RY20), "0" is set in this signal.
RX21
Frequency setting completion (RAM)
After "1" is set in the frequency setting command (RY21) and the set frequency is
written to the inverter RAM, "1" is set in this signal.
When "0" is set in the frequency setting command (RY21), "0" is set in this signal.
RX22
Frequency setting completion (RAM,
EEPROM)
After "1" is set in the frequency setting command (RY22) and the set frequency is
written to the inverter RAM and EEPROM, "1" is set in this signal.
When "0" is set in the frequency setting command (RY22), "0" is set in this signal.
RX23
Torque command / torque limit setting
completion (RAM)
After "1" is set in the torque command / torque limit (RY23) and the torque command
/ torque limit value is written to the inverter RAM, "1" is set in this signal.
When "0" is set in the torque command / torque limit (RY23), "0" is set in this signal.
RX24
Torque command / torque limit setting
completion (RAM, EEPROM)
After "1" is set in the torque command / torque limit (RY24) and the torque command
/ torque limit value is written to the inverter RAM and EEPROM, "1" is set in this signal.
When "0" is set in the torque command / torque limit (RY24), "0" is set in this signal.
RX25
Instruction code execution completion
After "1" is set in the instruction code execution request (RY25) and the processes
corresponding to the instruction codes (RWw10, 12, 14, 16, 18 and 1A) are executed,
"1" is set in this signal. When "0" is set in the instruction code execution request
(RY25), "0" is set in this signal.
RX3A
Error status flag
When an inverter error occurs (protective function is activated), "1" is set in this signal.
RX3B
Remote station ready
When the inverter goes into the ready status upon completion of initial setting after
power-ON or hardware reset, "1" is set in this signal. When an inverter error occurs
(protective function is activated), "0" is set in this signal. The signal is used as an
interlock signal during the write to/read from the master module.
Tab. 5-347:
Output signals from the inverter
Device No.
Signal
Description
Tab. 5-346:
Output signals from the master module(2)
Summary of Contents for FR-A820-00046 (0.4K)
Page 2: ......
Page 4: ......
Page 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Page 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Page 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1190: ...EC Declarations of Conformity Appendix A 50 ...
Page 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Page 1192: ...EC Declarations of Conformity Appendix A 52 ...
Page 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1194: ...EC Declarations of Conformity Appendix A 54 ...
Page 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1196: ...EC Declarations of Conformity Appendix A 56 ...
Page 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Page 1198: ...EC Declarations of Conformity Appendix A 58 ...
Page 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Page 1200: ...EC Declarations of Conformity Appendix A 60 ...
Page 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Page 1202: ...EC Declarations of Conformity Appendix A 62 ...
Page 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Page 1204: ...EC Declarations of Conformity Appendix A 64 ...
Page 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Page 1206: ...EC Declarations of Conformity Appendix A 66 ...
Page 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Page 1208: ...EC Declarations of Conformity Appendix A 68 ...
Page 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Page 1210: ...EC Declarations of Conformity Appendix A 70 ...
Page 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Page 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Page 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Page 1214: ...EC Declarations of Conformity Appendix A 74 ...
Page 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Page 1217: ......