(M) Monitor display and monitor output signal
Parameters
5 - 384
Adjusting the output terminal response level (Pr. 289)
The response level of the output terminals can be delayed in a range of 5 to 50 ms. (Operation example
for the RUN signal.)
Inverter operation ready signals (RY, RY2 signals)
and inverter running signals (RUN, RUN2, RUN3 signals)
●
Operation under V/F control and Advanced magnetic flux vector control
–
When the inverter is ready for operation, the Inverter operation ready (RY) signal turns ON
(stays ON during operation.)
–
When the inverter output frequency reaches Pr. 13 "Starting frequency" or higher, the Inverter
running (RUN, RUN2) signals turn ON. The signal is OFF while the inverter is stopped and during
DC injection brake operation.
–
The Inverter running and start command is ON (RUN3) signal is ON while the inverter is running
or the start signal is ON. (When the start command is ON, the RUN3 signal output turns ON
even while the inverter's protective function is activated or the MRS is ON.) During DC injection
brake operation as well, the output is ON, and when the inverter stops, it turns OFF.
Fig. 5-168:
Adjusting the RUN signal response level
I002620E
NOTES
When Pr. 157 "OL signal output timer" is set for the Overload warning (OL) signal output, the OL
signal is output when the set time of (Pr. 157 + Pr. 289) elapses.
For the output signal and the fault code output (on page 5-399) used in the PLC function (on page
5-606), the Pr. 289 setting is invalid (no filter).
I002621E
Fig. 5-169:
Ready and motor running signals
RUN
Pr. 289 ≠ 9999
Pr. 289
Pr. 289
OFF
OFF
ON
ON
Time
RUN
Pr. 289 = 9999
Output fr
equen
cy
STF
RH
RY
RUN3
RUN
(RUN2)
Pr. 13
Reset
processing
Power supply
DC injection brake
operation point
DC injection
brake
operation
Time
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
OFF
OFF
Ou
tput fr
equenc
y
Summary of Contents for FR-A820-00046 (0.4K)
Page 2: ......
Page 4: ......
Page 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Page 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Page 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1190: ...EC Declarations of Conformity Appendix A 50 ...
Page 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Page 1192: ...EC Declarations of Conformity Appendix A 52 ...
Page 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1194: ...EC Declarations of Conformity Appendix A 54 ...
Page 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1196: ...EC Declarations of Conformity Appendix A 56 ...
Page 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Page 1198: ...EC Declarations of Conformity Appendix A 58 ...
Page 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Page 1200: ...EC Declarations of Conformity Appendix A 60 ...
Page 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Page 1202: ...EC Declarations of Conformity Appendix A 62 ...
Page 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Page 1204: ...EC Declarations of Conformity Appendix A 64 ...
Page 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Page 1206: ...EC Declarations of Conformity Appendix A 66 ...
Page 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Page 1208: ...EC Declarations of Conformity Appendix A 68 ...
Page 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Page 1210: ...EC Declarations of Conformity Appendix A 70 ...
Page 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Page 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Page 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Page 1214: ...EC Declarations of Conformity Appendix A 74 ...
Page 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Page 1217: ......