Protective functions
Check first when you have a trouble
FR-A800
6 - 47
6.6.9
Operation mode is not changed properly
6.6.10
Operation panel (FR-DU08) display is not operating
6.6.11
Motor current is too large
Check
points
Possible cause
Countermeasure
Refer to
page
Input
signal
Start signal (STF or STR) is ON.
Check that the STF and STR signals are off.
When either is ON, the operation mode cannot
be changed.
Parameter
setting
Pr. 79 "Operation mode selection" setting is
improper.
When the Pr. 79 is set to "0 (initial value)", the
operation mode is the External operation mode
at power ON. To switch to the PU operation
mode, press PU/EXT key on the operation panel
(press PU key on the parameter unit (FR-PU07)).
At other settings (1 to 4, 6, 7), the operation
mode is limited accordingly.
Operation mode and a writing device do
not correspond.
Check Pr. 79 "Operation mode selection", Pr. 338
"Communication operation command source",
Pr. 339 "Communication speed command
source", Pr. 550 "NET mode operation command
source selection" and Pr. 551 "PU mode
operation command source selection", and
select an operation mode suitable for the
purpose.
Check
points
Possible cause
Countermeasure
Refer to
page
Main
circuit
Power is not input.
Input the power.
Control
circuit
Front
cover
Operation panel is not properly connected
to the inverter.
Check if the inverter front cover is installed
securely.
Check
points
Possible cause
Countermeasure
Refer to
page
Parameter
setting
Torque boost (Pr. 0, Pr. 46, Pr. 112) setting is
improper under V/F control, so the stall
prevention function is activated.
Increase/decrease the Pr. 0 "Torque boost"
setting value by 0.5% increments so that stall
prevention does not occur.
V/F pattern is improper when V/F control is
performed.
(Pr. 3, Pr. 14, Pr. 19)
Set rated frequency of the motor to Pr. 3 "Base
frequency".
Use Pr. 19 "Base frequency voltage" to set the
base voltage (for example, rated motor
voltage).
Change Pr. 14 "Load pattern selection"
according to the load characteristic.
Stall prevention (torque limit) function is
activated due to a heavy load.
Reduce the load weight.
⎯
Set Pr. 22 "Stall prevention operation level
(torque limit level)" higher according to the
load.
(If Pr.22 is set too high, an overcurrent trip
(E.OC
첸
) is likely to occur.)
Check the capacities of the inverter and the
motor.
⎯
Offline auto tuning is not performed under
Advanced magnetic flux vector control, Real
sensorless vector control, or vector control.
Perform offline auto tuning.
When PM sensorless vector control is
selected for an IPM motor other than
MM-CF, and offline auto tuning is not
performed.
Perform offline auto tuning for an IPM motor.
Summary of Contents for FR-A820-00046 (0.4K)
Page 2: ......
Page 4: ......
Page 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Page 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Page 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1190: ...EC Declarations of Conformity Appendix A 50 ...
Page 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Page 1192: ...EC Declarations of Conformity Appendix A 52 ...
Page 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1194: ...EC Declarations of Conformity Appendix A 54 ...
Page 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1196: ...EC Declarations of Conformity Appendix A 56 ...
Page 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Page 1198: ...EC Declarations of Conformity Appendix A 58 ...
Page 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Page 1200: ...EC Declarations of Conformity Appendix A 60 ...
Page 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Page 1202: ...EC Declarations of Conformity Appendix A 62 ...
Page 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Page 1204: ...EC Declarations of Conformity Appendix A 64 ...
Page 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Page 1206: ...EC Declarations of Conformity Appendix A 66 ...
Page 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Page 1208: ...EC Declarations of Conformity Appendix A 68 ...
Page 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Page 1210: ...EC Declarations of Conformity Appendix A 70 ...
Page 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Page 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Page 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Page 1214: ...EC Declarations of Conformity Appendix A 74 ...
Page 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Page 1217: ......