(F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
Parameters
5 - 264
Shortest acceleration/deceleration (Pr. 292 = "1, 11", Pr. 293)
●
Set this parameter to accelerate/decelerate the motor at the shortest time. This function is useful
when the motor needs to be accelerated/decelerated at a shorter time, such as for a machine, but
the designed value of the machine constant is not known.
●
This function adjusts the acceleration/deceleration time to accelerate/decelerate the motor with
the maximum torque that can be output with the inverter. Pr. 7 "Acceleration time" and Pr. 8
"Deceleration time" settings are used as reference, and their settings are not changed.
●
Use Pr. 293 "Acceleration/deceleration separate selection" to apply the shortest acceleration/
deceleration to one of acceleration and deceleration only.
When "0 (initial value)" is set, the shortest acceleration/deceleration is performed for both accel-
eration and deceleration.
●
Since the FR-A820-00490(7.5K) or lower, FR-A840-00250(7.5K) or lower capacity inverters are
equipped with built-in brake resistors, set Pr. 292 to "11". Set "11" also when a high-duty brake
resistor or brake unit is connected. The deceleration time can further be shortened.
●
When the shortest acceleration/deceleration is selected under V/F control and Advanced mag-
netic flux vector control, the stall prevention operation level during acceleration/deceleration
becomes 150% (adjustable using Pr. 61 to Pr. 63). The setting of Pr. 22 "Stall prevention operation
level" and stall level by analog input are used only during a constant speed operation.
Under Real sensorless vector control and vector control, the torque limit level (Pr. 22, etc.) is
applied during acceleration/deceleration. The adjustments by Pr. 61 to Pr. 63 are disabled.
●
It is inappropriate to use for the following applications.
–
Machines with large inertia (10 times or more), such as a fan. Since stall prevention operation
will be activated for a long time, this type of machine may trip due to motor overloading, etc.
–
When the inverter is always operated at a specified acceleration/deceleration time.
NOTES
Even if automatic acceleration/deceleration has been selected, inputting the JOG signal (JOG
operation), RT signal (second function selection) or X9 signal (third function selection) during an
inverter stop will switch to the normal operation and give priority to JOG
operation, second function selection or third function selection. Note that during operation, an
input of JOG and RT signal does not have any influence even when the automatic acceleration/
deceleration is enabled.
Since the shortest acceleration/deceleration is made with the stall prevention operation being
activated, the acceleration/deceleration speed always varies according to the load conditions.
By setting Pr. 7 and Pr. 8 appropriately, it is possible to accelerate/decelerate with a shorter time
than when selecting the shortest acceleration/deceleration.
Summary of Contents for FR-A820-00046 (0.4K)
Page 2: ......
Page 4: ......
Page 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Page 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Page 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1190: ...EC Declarations of Conformity Appendix A 50 ...
Page 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Page 1192: ...EC Declarations of Conformity Appendix A 52 ...
Page 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1194: ...EC Declarations of Conformity Appendix A 54 ...
Page 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1196: ...EC Declarations of Conformity Appendix A 56 ...
Page 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Page 1198: ...EC Declarations of Conformity Appendix A 58 ...
Page 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Page 1200: ...EC Declarations of Conformity Appendix A 60 ...
Page 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Page 1202: ...EC Declarations of Conformity Appendix A 62 ...
Page 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Page 1204: ...EC Declarations of Conformity Appendix A 64 ...
Page 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Page 1206: ...EC Declarations of Conformity Appendix A 66 ...
Page 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Page 1208: ...EC Declarations of Conformity Appendix A 68 ...
Page 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Page 1210: ...EC Declarations of Conformity Appendix A 70 ...
Page 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Page 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Page 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Page 1214: ...EC Declarations of Conformity Appendix A 74 ...
Page 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Page 1217: ......