Installation and wiring
Connection of stand-alone option units
FR-A800
2 - 99
2.10.6
Connection of the power regeneration common converter (FR-CV)
When connecting the power regeneration common converter (FR-CV), connect the inverter terminals
(P/+, N/-) and the power regeneration common converter (FR-CV) terminals as shown below so that
their symbols match with each other.
The FR-CV is applicable to the FR-A820-03160(55K) or lower and the FR-A840-01800(55K) or lower.
After making sure that the wiring is correct, set "2" in Pr. 30 "Regenerative function selection". (Refer
to page 5-713.)
Remove jumpers between terminals R/L1 and R1/L11 as well as between S/L2 and S1/L21, and
connect the power supply for the control circuit to terminals R1/L11 and S1/L21. Do not connect
anything to power input terminals (R/L1, S/L2, T/L3). Incorrect connection will damage the inverter.
(E.OPT (option fault) will occur. (Refer to page 6-28.)
Do not insert an MCCB between terminals P/+ and N/- (between terminals P/L+ and P/+ or
between N/L- and N/-). Connecting the opposite polarity of terminals N/- and P/+ will damage the
inverter.
Use Pr. 178 to Pr. 189 (input terminal function selection) to assign the terminals used for the X10
signal. (Refer to page 5-439.)
Be sure to connect the power supply and terminals R/L11, S/L21, and T/MC1. Operating the inverter
without connecting them will damage the power regeneration common converter.
$
Always connect terminal RDYB of the FR-CV to the inverter terminal where the X10 signal or the
MRS signal is assigned to. Always connect terminal SE of the FR-CV to the inverter terminal SD. Not
connecting these terminals may damage the FR-CV.
I001039E
Fig. 2-69:
Connection of the power regeneration common converter (FR-CV)
NOTES
The voltage phases of terminals R/L11, S/L21, and T/MC1 and the voltage phases of terminals R2/L1,
S2/L2, and T2/L3 must be matched.
Use the sink logic (factory setting) when the FR-CV is connected. It cannot be connected when the
source logic is selected.
Do not connect a DC reactor (FR-HEL) to the inverter when FR-CV is connected.
M
3~
Three-
phase AC
power
supply
$
Inverter
Dedicated stand-alone
reactor (FR-CVL)
FR-CV type
Power regeneration common
converter
Summary of Contents for FR-A820-00046 (0.4K)
Page 2: ......
Page 4: ......
Page 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Page 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Page 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1190: ...EC Declarations of Conformity Appendix A 50 ...
Page 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Page 1192: ...EC Declarations of Conformity Appendix A 52 ...
Page 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1194: ...EC Declarations of Conformity Appendix A 54 ...
Page 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1196: ...EC Declarations of Conformity Appendix A 56 ...
Page 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Page 1198: ...EC Declarations of Conformity Appendix A 58 ...
Page 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Page 1200: ...EC Declarations of Conformity Appendix A 60 ...
Page 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Page 1202: ...EC Declarations of Conformity Appendix A 62 ...
Page 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Page 1204: ...EC Declarations of Conformity Appendix A 64 ...
Page 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Page 1206: ...EC Declarations of Conformity Appendix A 66 ...
Page 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Page 1208: ...EC Declarations of Conformity Appendix A 68 ...
Page 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Page 1210: ...EC Declarations of Conformity Appendix A 70 ...
Page 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Page 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Page 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Page 1214: ...EC Declarations of Conformity Appendix A 74 ...
Page 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Page 1217: ......