Parameters
Speed control under Real sensorless vector control, vector control, PM sensorless vector control
FR-A800
5 - 101
Trip during torque limit operation (Pr. 874)
●
A trip can be set for when the torque limit is activated and the motor stalls.
●
When a high load is applied and the torque limit is activated under speed control or position
control, the motor stalls. At this time, if a state where the rotation speed is lower than the value
set in Pr. 865 "Low speed detection" and the output torque exceeds the level set in Pr. 874 "OLT
level setting" continues for 3 s, Stall prevention stop (E.OLT) is activated and the inverter output
is shut off.
Adjusting the stall prevention operation signal and output timing (OL signal, Pr. 157)
●
If the output torque exceeds the torque limit level and the torque limit is activated, the stall
prevention operation signal (OL signal) is turned ON for 100 ms or longer. When the output torque
drops to the torque limit level or lower, the output signal also turns OFF.
●
Pr. 157 "OL signal output timer" can be used to set whether to output the OL signal immediately,
or whether to output it after a certain time period has elapsed.
I001508E
Fig. 5-22:
Alarm stop when torque limit is activated
NOTES
Under V/F control or Advanced magnetic flux vector control, if the output frequency drops to
0.5 Hz due to the stall prevention operation and this state continues for 3 s, a fault indication
(E.OLT) appears, and the inverter output is shut off. This operation is activated regardless of the
Pr. 874 setting.
This fault does not occur under the torque control.
Pr. 157 setting
Description
0 (Initial value)
Output immediately.
0.1 to 25
Output after the set time (s).
9999
Not output.
Tab. 5-33:
Setting of parameter 157
Output
frequency [Hz]
Start signal (STF)
Fault signal (ALM)
Pr. 865
Pr. 874
Torque
Output torque
Torque limit
3 s
E.OLT occurrence
Time
Time
Summary of Contents for FR-A820-00046 (0.4K)
Page 2: ......
Page 4: ......
Page 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Page 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Page 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1190: ...EC Declarations of Conformity Appendix A 50 ...
Page 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Page 1192: ...EC Declarations of Conformity Appendix A 52 ...
Page 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1194: ...EC Declarations of Conformity Appendix A 54 ...
Page 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1196: ...EC Declarations of Conformity Appendix A 56 ...
Page 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Page 1198: ...EC Declarations of Conformity Appendix A 58 ...
Page 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Page 1200: ...EC Declarations of Conformity Appendix A 60 ...
Page 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Page 1202: ...EC Declarations of Conformity Appendix A 62 ...
Page 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Page 1204: ...EC Declarations of Conformity Appendix A 64 ...
Page 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Page 1206: ...EC Declarations of Conformity Appendix A 66 ...
Page 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Page 1208: ...EC Declarations of Conformity Appendix A 68 ...
Page 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Page 1210: ...EC Declarations of Conformity Appendix A 70 ...
Page 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Page 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Page 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Page 1214: ...EC Declarations of Conformity Appendix A 74 ...
Page 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Page 1217: ......