(M) Monitor display and monitor output signal
Parameters
5 - 386
–
The RUN2 and RUN3 signals also are ON when the start command is ON and when pre-
excitation is operating with the speed command = 0. (However, the RUN2 signal is OFF during
pre-excitation operation activated by LX signal ON.)
–
The Operation ready 2 (RY2) signal turns ON when the pre-excitation starts. It stays ON while
pre-excitation is operating even when the inverter is stopped.
●
According to the inverter condition, the ON/OFF operation of each signal is as shown below.
When the start signal is ON and the frequency command is 0 Hz, pre-excitation is entered.
Turns OFF during power failure or undervoltage.
A delay of 100 ms (500 ms for FR-A820-03800(75K) or higher, FR-A840-02160(75K) or higher) occurs
when turned ON.
Turns ON while the servo is ON (LX signal ON) under position control.
$
Output is shutoff in conditions like a fault and when the MRS signal is ON.
%
OFF while power is not supplied to the main circuit power supply.
NOTE
When pre-excitation is activated by the pre-excitation signal (LX), the RY2 signal turns ON 100 ms
(500 ms for FR-A820-03800(75K) or higher, FR-A840-02160(75K) or higher) after the LX signal turns
ON. (When online auto tuning at start-up (Pr. 95 = "1") is selected, the ON timing is delayed by the
tuning time.)
Output
signal
Start
signal
OFF
(during
stop)
Start
signal
(pre-
excita-
tion)
Start
signal
ON
(run-
ning)
LX
signal
ON
(pre-
excita-
tion)
DC injec-
tion brake
operating
(pre-
excitation)
Output shutoff
Automatic restart after
instantaneous power failure
Coasting
Restart-
ing
Start
signal
ON
Start
signal
OFF
Start
signal
ON
Start
signal
OFF
ON
ON
ON
ON
ON
OFF
ON
RY2
OFF
ON
ON
ON
OFF
OFF
OFF
RUN
OFF
OFF
ON
OFF
OFF
OFF
ON
RUN2
OFF
ON
ON
OFF
OFF
OFF
ON
RUN3
OFF
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
Tab. 5-146:
Output signal output
LX
RY2
ON
ON
100 (500) ms
Summary of Contents for FR-A820-00046 (0.4K)
Page 2: ......
Page 4: ......
Page 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Page 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Page 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Page 1190: ...EC Declarations of Conformity Appendix A 50 ...
Page 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Page 1192: ...EC Declarations of Conformity Appendix A 52 ...
Page 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Page 1194: ...EC Declarations of Conformity Appendix A 54 ...
Page 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Page 1196: ...EC Declarations of Conformity Appendix A 56 ...
Page 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Page 1198: ...EC Declarations of Conformity Appendix A 58 ...
Page 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Page 1200: ...EC Declarations of Conformity Appendix A 60 ...
Page 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Page 1202: ...EC Declarations of Conformity Appendix A 62 ...
Page 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Page 1204: ...EC Declarations of Conformity Appendix A 64 ...
Page 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Page 1206: ...EC Declarations of Conformity Appendix A 66 ...
Page 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Page 1208: ...EC Declarations of Conformity Appendix A 68 ...
Page 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Page 1210: ...EC Declarations of Conformity Appendix A 70 ...
Page 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Page 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Page 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Page 1214: ...EC Declarations of Conformity Appendix A 74 ...
Page 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Page 1217: ......