3. Make sure that the heat sink for microprocessor n.
4. (Trained technician only) Replace system board.
•
80010901-2d01xxxx : Numeric sensor [NumericSensorElementName] going high (upper critical)
has asserted. (PCH Temp)
This message is for the use case when an implementation has detected an Upper Critical sensor going
high has asserted.
May also be shown as 800109012d01xxxx or 0x800109012d01xxxx
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix:
PLAT
ID:
0494
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and
rear of the server), that the air baffle is in place and correctly installed, and that the server cover
is installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications (see Server
Features and specifications for more information).
3. Make sure that the heat sink for microprocessor n.
4. (Trained technician only) Replace system board.
•
80010901-3701xxxx : Numeric sensor [NumericSensorElementName] going high (upper critical)
has asserted. (Ambient Temp)
This message is for the use case when an implementation has detected an Upper Critical sensor going
high has asserted.
May also be shown as 800109013701xxxx or 0x800109013701xxxx
Severity
Error
Serviceable
Yes
386
System x3500 M5 Installation and Service Guide
Summary of Contents for System x3500 M5 Type 5464
Page 1: ...System x3500 M5 Installation and Service Guide Machine Type 5464 ...
Page 6: ...iv System x3500 M5 Installation and Service Guide ...
Page 16: ...xiv System x3500 M5 Installation and Service Guide ...
Page 140: ...124 System x3500 M5 Installation and Service Guide ...
Page 194: ...178 System x3500 M5 Installation and Service Guide ...
Page 1056: ...1040 System x3500 M5 Installation and Service Guide ...
Page 1214: ...1198 System x3500 M5 Installation and Service Guide ...
Page 1218: ...1202 System x3500 M5 Installation and Service Guide ...
Page 1226: ...Taiwan BSMI RoHS declaration 1210 System x3500 M5 Installation and Service Guide ...
Page 1235: ......
Page 1236: ......