Automatically notify support
No
Alert Category
Warning - Temperature
SNMP Trap ID
12
CIM Information
Prefix:
PLAT
ID:
0490
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and
rear of the server), that the air baffle is in place and correctly installed, and that the server cover
is installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications (see Server
Features and specifications for more information).
3. Make sure that the heat sink for microprocessor n.
4. (Trained technician only) Replace system board.
•
80010701-1402xxxx : Numeric sensor [NumericSensorElementName] going high (upper
non-critical) has asserted. (CPU2 VR Temp)
This message is for the use case when an implementation has detected an Upper Non-critical sensor
going high has asserted.
May also be shown as 800107011402xxxx or 0x800107011402xxxx
Severity
Warning
Serviceable
Yes
Automatically notify support
No
Alert Category
Warning - Temperature
SNMP Trap ID
12
CIM Information
Prefix:
PLAT
ID:
0490
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and
rear of the server), that the air baffle is in place and correctly installed, and that the server cover
is installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications (see Server
Features and specifications for more information).
Appendix A. Integrated Management Module II (IMM2) error messages
377
Summary of Contents for System x3500 M5 Type 5464
Page 1: ...System x3500 M5 Installation and Service Guide Machine Type 5464 ...
Page 6: ...iv System x3500 M5 Installation and Service Guide ...
Page 16: ...xiv System x3500 M5 Installation and Service Guide ...
Page 140: ...124 System x3500 M5 Installation and Service Guide ...
Page 194: ...178 System x3500 M5 Installation and Service Guide ...
Page 1056: ...1040 System x3500 M5 Installation and Service Guide ...
Page 1214: ...1198 System x3500 M5 Installation and Service Guide ...
Page 1218: ...1202 System x3500 M5 Installation and Service Guide ...
Page 1226: ...Taiwan BSMI RoHS declaration 1210 System x3500 M5 Installation and Service Guide ...
Page 1235: ......
Page 1236: ......